6| Commissioning
6.8 Connection of oil level regulator
The connection "O" is provided for installing an oil level regulator. A corresponding adapter must be
obtained from the trade.
7| Maintenance
7.1 Preparation
D
GB
7.2 Work to be carried out
F
In order to guarantee optimum operational reliability and service life of the compressor, we recommend
E
carrying out servicing and inspection work at regular intervals:
Oil change:
-
not mandatory for factory-produced series systems.
-
f or field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.
Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
a uxiliary devices such as oil sump heater, pressure switch.
7.3 Spare parts recommendation
HA12P / ...
Designation
Set of gaskets
Valve plate kit
Oil pump kit
Oil sump heater kit
110-240 V
Only use genuine Bock spare parts!
20
WARNING! Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch-on lock.
60-4
Ref. No.
75-4
Ref. No.
80339
80352
08324
08028
90-4
110-4
Ref. No.
Ref. No.
80353