Huawei iBAT 2.0-CIM01C2 User Manual page 21

Hide thumbs Also See for iBAT 2.0-CIM01C2:
Table of Contents

Advertisement

iBAT 2.0-CIM01C2
User Manual
BIM
BIM01C3
BIM02C1
Appearance
Figure 2-8 BIM appearance
(1) RUN/ALM indicator
Issue 07 (2019-01-02)
Description
When the battery supply voltage is lower than 9.6 V for more than 30
minutes, the BIM automatically powers off.
When the BIM communication has failed for more than 30 minutes and the
battery voltage is lower than 12.6 V, the BIM automatically powers off.
When the BIM has not been networked successfully in more than two days
after power-on and the battery voltage is lower than 12.6 V, the BIM
automatically powers off.
When the battery supply voltage is lower than 1.6 V for more than 30
minutes, the BIM automatically powers off.
When the BIM communication has failed for more than 30 minutes and the
battery voltage is lower than 2.1 V, the BIM automatically powers off.
When the BIM has not been networked successfully in more than two days
after power-on and the battery voltage is lower than 2.1 V, the BIM
automatically powers off.
(2) Networking switch
Copyright © Huawei Technologies Co., Ltd.
2 Overview
(3) Panel port
(4) Fastener
15