Installation Instructions

3.Power cord connection

CAUTION
CAUTION
Electric wiring cautions
Work in accordance with the electric local wiring rules and standards and the working standard specified by the power company.
In order to avoid motor burn-out due to over current, be sure to mount an overload protection device (such as the motor
breaker) that matches the ratings on each fan.
(Select a motor breaker that supports the maximum current multiplied by 1.2 to 1.5 (described in the "Specifications"
on page 8).)
Always install the earth leakage breaker.
Connect the power cord shown as dotted lines in the "Wiring Diagram".
Open the terminal cover and pass power cord through the gum grommet.
Connect the power cord according to the "Wiring Diagram", "Power cord treatment" (on rear cover page) and "Connecting
wiring" (on rear cover page).
When connecting the power cord, fix the power cord to the hanging
bolt so that the power connector is not under tension.
(The K25DSF2NET do not have terminal covers.)
As water may enter the connector along the power cord, use a trap
or other type of treatment for the power cord (see illustration at right).
After the power cord has been connected, always mount the terminal cover.
(Except K25DSF2NET.)
A thermal fuse is mounted inside the motor of this product for protection.
If the source voltage differs from ratings or if power cord is not correctly
connected, the temperature of the motor windings may increase. In this
case, the thermal fuse will blow and the motor will stop. Once the fuse
blows, the motor cannot restart itself (that is, it cannot rotate).
Locate and remove the cause of the error, and replace the motor.
Note that an unstable (or temporarily installed) power supply may cause the thermal fuse to blow and the motor may stop
during a trial run.
After wiring, check the rotation direction in case of three phase motors.
Hi
WIRING
POWER
SUPPLY
DIAGRAM
(SINGLE PHASE)
K25DSF2NET
K28DSM2NET
Lo
K35DSM2NET
K40DSL2NET
K40DSH2NET
POWER
K45DST2NET
SUPPLY
[
K25DSF2NET:
・ There is no connecting terminal.
・ The tip of the unused cord must be insulated.
CAUTION
In order to avoid the danger, it must be connected by qualified technician.
Incorrect wiring may result in current leakage or fire.
This product must be properly and reliably grounded.
There is a possibility of receiving an electric shock.
MOTOR
Red
Hi
Wht
N
Blk
Lo
CAPACITOR
MOTOR
Red
Hi
Wht
N
Blk
Lo
CAPACITOR
]
Exercise care when you connect cords.
When operating the motor while using the different source voltage from ratings, if you
arrange the cabling differently from that shown in the wiring diagram, or if you mistake
single-phase for three-phase, the motor may burn out.
Connector (inside the terminal cover)
Power cord
Hi
POWER
WIRING
SUPPLY
DIAGRAM
(THREE PHASE)
K40DTL2BET
K40DTH2BET
K45DTT2BET
K45DTH2BET
Lo
POWER
SUPPLY
Terminal cover
(It is not supplied with K25DSF2NET.)
Hanging
Fixing
bolt
band
Power cord
Trap
Red
R
U
Wht
S
V
MOTOR
Blk
T
W
Brw
U1
Yel
V1
Blu
W1
Red
U
Wht
V
MOTOR
Blk
W
Brw
R
U1
Yel
S
V1
Blu
T
W1
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents