Mains Input Electrical Specifications - Huawei UPS2000-G Series User Manual

Hide thumbs Also See for UPS2000-G Series:
Table of Contents

Advertisement

UPS2000-G-(1 kVA-3 kVA)
User Manual
Item
Defend Level

9.3 Mains Input Electrical Specifications

Table 9-3 Mains input electrical specifications
Item
Input power cable
Rated input voltage
Input
voltage
range
Input power factor
(100% resistive load)
Startup voltage
Diesel generator input
capacity
Issue 15 (2019-12-19)
1 kVA
IP20
1 kVA
Single-phase (L/N) input +PE cable
200V AC/208V AC/220V AC/230V AC/240V AC
Lowest
When the ambient temperature is 0–35° C:
conversion
160/140/120/110 V AC (tolerance ± 5%)
voltage
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
When the ambient temperature is 35–40° C:
175/155/135/125 V AC (tolerance ± 5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
Lowest
When the ambient temperature is 0–35° C:
recovery
175/155/135/125 V AC (tolerance ± 5%)
voltage
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
When the ambient temperature is 35–40° C:
190/170/150/140 V AC (tolerance ± 5%)
(Ratio of actual load to rated load:
100%–80%/80%–70%/70%–60%/60%–0)
Highest
300 V AC (tolerance ± 5%, load percentage < 80%)
conversion
280 V AC (tolerance ± 5%, 80% < load percentage < 100%,
voltage
after 15 minutes to battery mode)
Highest
290 V AC (tolerance ± 5%, load percentage < 80%)
recovery
270 V AC (tolerance ± 5%, 80% < load percentage < 100%)
voltage
> 0.99
120 V-280 V AC
Minimum 1.5 times the UPS rated capacity
Copyright © Huawei Technologies Co., Ltd.
2 kVA
2 kVA
9 Specifications
3 kVA
3 kVA
73