D7039 | Installation Guide |
Notices
Use these instructions to install the D7039 Multiplex
Expansion Module in a fire system supervised by a
D7024 Fire Alarm Control Panel (FACP).
Install, test, and maintain the D7039 according to these
instructions, NFPA 72, local codes, and the Authority
Having Jurisdiction (AHJ).
Follow the procedures in this document to
avoid personal injury and damage to the
equipment. Failure to follow these
procedures can cause the D7039 to not
operate properly. Bosch is not responsible
for improperly installed, tested, or maintained
devices.
For the D7039 with ROM version 1.04 to
operate properly, the D7024 FACP must be
running version 2.05 or later firmware.
2
Notices
1.0

Description

The D7039 (Figure 1) connects directly to the FACP for
either two Class B multiplex buses or one Class A
multiplex bus that allows up to 247 remote points.
Figure 1: D7039 Module Location
Power
Alarm
1
2
4
4 5 6
7 8 9
*
0
C lear
Prog
1 - D7024 Control Board
2 - Enclosure
3 - I/O module for the D7039
4 - D7039 Module
When configured for Class A operation,
the D7039 can only support Addresses 9
through 128.
1
Trouble
Silenced
3
Drill
Silence
Disable
Test
Reset
#
History
Cmnd
Bosch | 09/05 | 38685F