Temporary Removal Of The Device; Remote Control And Remote Transmission Of Messages; Potential-Free Input - Judo PROFIMAT JPF-A Series Installation And Operating Instructions Manual

Automatic backwash protective filter
Table of Contents

Advertisement

5.5
Temporary removal of the
device
WARNING
If the device is removed due to an
interruption of operation:
• Protect the flange surfaces
against damage to ensure proper
sealing.
• Protect the device from dirt so
as not to impair drinking water
hygiene.
• Store the device in a frost-free
place to prevent damage caused
by freezing water and leakage.
When recommissioning the device, proceed
as with a new installation.
18
Operation
6
Remote control and
remote transmission of
messages
The following chapters are only rele-
INFO_NO_HEADER
vant for the " potential-free " version.
A peripheral device for controlling the
backwash and for transmitting back-
washing and fault indication can be
connected to this type of device.
The device may only be installed
ELECTRO_NO_HEADER
by qualified technical personnel.
The power supply unit must be
connected to make the electrical
installation and to adjust the DIP
switch.
On "potential-free" designs: Only
low voltages can be used for the
remote transmission of the fault
indication via the potential-free
output!
Switching voltage: maximum 24 V
Amperage: maximum 1 A
6.1

Potential-free input

The device has an additional input to which
a peripheral can be connected for control
and an additional DIP switch for setting the
backwash mode for remote control.
Setting the potential-free input
WARNING
The power supply unit must be
connected to make the electrical
installation and to adjust the DIP
switch.
JUDO JPF-A
1701649 • 2019/04