Page 1
Installation and operating instructions JUDO PROFI-PLUS Backwash protective filter ¾" - 2" Valid for: EU countries and Switzerland Language: English Attention: Carefully read through the instal- lation and operating instructions and safety information before installing and putting the unit into service.
10.1 JPF-QC ¾" - 1¼" ......24 safe and proper work must also be 10.2 JPF-QC 1½" - 2" ......26 observed. 11. Customer service ......28 Therefore, this instruction manual must always be read by the fitter and responsible JUDO PROFI-PLUS / JUDO PROFI-QC...
The use of the device in accordance with the customer’s specifications includes observance of the operating instructions. manufacturer/supplier should consulted prior to any operation of the filter other than in the operational areas stated in these operating instructions. JUDO PROFI-PLUS / JUDO PROFI-QC...
In the event of such cases persons are at risk and may sustain electrical shocks. Therefore any electrical devices/installations situated in the direct vicinity should be splash-water proof or comply with the statutory requirements for wet areas. JUDO PROFI-PLUS / JUDO PROFI-QC...
KTW guideline of the German Fed- eral Environmental Agency as well as the DVGW working sheet W 270. Metallic mate- rials fulfil the requirements of DIN 50930-6 (Impact on the drinking water quality). JUDO PROFI-PLUS / JUDO PROFI-QC...
– It is not permitted to install the Backwash protective filter upstream of the water meter! The shipping carton can be slipped over the built-in filter to prevent damage, for instance at construc- tion sites. JUDO PROFI-PLUS / JUDO PROFI-QC...
Page 10
In this case, people close to the filter are ex- water escaping. This can in turn cause water posed to a health risk due to the large quan- damage to the house and its installations tities of water. (see fig. 4). JUDO PROFI-PLUS / JUDO PROFI-QC...
– When the bucket is half-filled the back- washing process must be stopped. Oth- erwise it is possible for the bucket to overflow. Therefore the bucket must be adequately dimensioned and the back- washing should be carried out quickly. JUDO PROFI-PLUS / JUDO PROFI-QC...
Page 12
> 100 mm > 100 mm > 100 mm > 100 mm > 200 mm > 200 mm min.15 l min.10 l > 40 mm > 20 mm > 40 mm Fig. 5: Backwashing water discharge options JUDO PROFI-PLUS / JUDO PROFI-QC...
Insert the two included batteries in the battery compartment. Use 1.5 V Micro batteries. Fig. 6: Functional description • Replace the handwheel lid. • You can test the functionality by pressing the -key in the lid of RESET the handwheel. JUDO PROFI-PLUS / JUDO PROFI-QC...
Water inlet the sieve cloth in the fine filter (12) but also b Filtered water the transparent filter hood (6) using a rubber lip on its exterior side. JUDO PROFI-PLUS / JUDO PROFI-QC...
Page 15
Unauthorised persons must not operate the filter! Persons who operate the filter must observe the operating instructions. Failure to observe these instructions can result in damage to property and personal injuries. JUDO PROFI-PLUS / JUDO PROFI-QC...
The battery is used up. Replace the batteries with does not beep when the new ones! Return used bat- -key is pressed. teries to the collection cen- tres! (only JPF ¾" - 1¼") JUDO PROFI-PLUS / JUDO PROFI-QC...
ATTENTION (see chapter “Safety information dangers due to non-compliance”) To make sure the total interval of two- months is not exceeded, backwash the filter after replacing the batteries. JUDO PROFI-PLUS / JUDO PROFI-QC...
(see chapter 5.3.1). DIN EN 13443-1 specifies that backwashing must take place at least every six months. However, JUDO recommends to carry out backwashing every two months! In order to achieve an operation success also after the putting into service and over many years, regular inspection and routine servicing of the unit are indispensable.
0.03 mm, 0.32 mm and 0.5 mm are available for technical and industrial use. Filters with special mesh sizes are not sub- ject to tests according to DIN 19632 and for this reason are not allowed to bear the DVGW mark. JUDO PROFI-PLUS / JUDO PROFI-QC...
0.3 - 0.8 l/s JPF-QC 2" 10.2 kg 16.0 (22.0) m³/h 0.3 - 0.8 l/s The backwashing volumetric flow given applies to 2 - 3 bar mains pressure and for a com- pletely opened flushing water valve. JUDO PROFI-PLUS / JUDO PROFI-QC...
B = Unit width G = Connection dimension waste water C = Height above pipe centre G1 = Connection dimension waste water D = Height below pipe centre (alternative) E = Depth to pipe centre JUDO PROFI-PLUS / JUDO PROFI-QC...
Spare parts 10. Spare parts 10.1 JPF ¾" - 1¼" JUDO PROFI-PLUS / JUDO PROFI-QC...
Page 25
Cylinder screw M6x25 2010199 O-ring 6.5x6 Hose connection 1120310 Cover Filter funnel 1) AU = Accounting unit (Items without AU are only available in a set.) Replacement interval: *** = 3 years, **** = 4 years JUDO PROFI-PLUS / JUDO PROFI-QC...
Page 27
1607117 Hose connection 1607157 Profiled flange gasket Cylinder screw M8x30 1607116 1) AU = Accounting unit (Items without AU are only available in a set.) Replacement interval: *** = 3 years, **** = 4 years JUDO PROFI-PLUS / JUDO PROFI-QC...