13 Direct lighted burner
Dismantle burner chamber. Using a suitable
13.1
light source, check burner chamber for con-
tamination, damage and leakage
After cleaning downstream heating surfaces,
13.2
vacuum clean the burner chamber
13.3
Check flame pan for damage
Remove inspection cover plate and cleaning
13.4
cover from burner chamber. Remove all turbula-
tors and check general condition
Clean all downstream heating surface pipes
13.5
with a stainless steel brush and vacuum clean
the collector tank
13.6
Check de-watering equipment
Subsequent to burner chamber cleaning, carry
13.7
out burner service and maintenance in accord-
ance with burner manufacturer's directives.
13.8
Determine exhaust gas value.
Check gas line, connections and gas control
13.9
path for leak-tightness
13.10
Check regulating and safety devices
13.11
Check bypass and burner chamber dampers
14 Gas burner
Check gas line, connections and gas control
14.1
path for leak-tightness
Remove any dirt particles from the burner with
14.2
a brush; ensure that all air holes are free
14.3
Check gas extract openings
14.4
Check ignition electrode gaps
Unscrew control monitor (UV cells or ionisa-
14.5
tions rod), clean with a soft cloth and re-install.
Replace if discolouration is detected
30
www.swegon.com
Activity
Action
Damaged burners must be put into service
Cleaning
In the event of damage or deformation,
restore or replace. For this, the burner plate
and cylinder cover must be dismantled.
In case of heavy corrosion, replace individu-
ally or completely.
Cleaning
Cleaning
Re-seal
Re-seal
Cleaning and repair
Clean with nozzle neele. Do not come in
contact with lignition or control devices
Adjust
Cleaning and repair
The company reserves the right to make design changes without prior notice.
EN.SILVER.110322
Months
1
3
6
12
24
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x