5.7 Droplet seperator

General
The droplet separator will bring its full effectiveness only
after a run-in period of ca. 4 weeks.
The droplet separator is to be cleaned by rinsing with
water as necessary. With large amounts of contamination,
cleaning can be done with a steam jet-spray unit.
An excessively contaminated and calcified droplet separa-
tor with a plugged drip-mould can lead to a droplet run-
off and increased pressure loss.
The droplet separator, possibly located downstream from,
and on the air-outlet-side of the air cooler, as a rule con-
tains lamella-fins, which are temperature resistant up to
+95°C.
Droplet separators are required only if the limiting speed
will be exceeded and a specific condensate volume is
present.
When cleaning the droplet separator, remove the car-
tridges and lamella-fins (remove bio-film).
During installation, heed air flow direction.
Commissioning
Check the droplet separator installation direction. The
drip-mould must indicate a direction opposite the air flow.
20
www.swegon.com

5.8 Cooling system

General
Because the cooling components in the air handling unit
have very differing designs, it is not possible in this context
to provide a detailed description of the work related to
commissioning, service and maintenance. The individual
operating instructions must be observed.
Bodily contact with refrigerant must be avoided, as freez-
ing of the skin and limbs or damage to the eye retina can
result. Equipment for personal protection against the
effects of refrigerant must be used in accordance with
national regulations!
Modifications to the system may be carried out only by
authorised specialist personnel.
The loose filter dryer included in the delivery may be
opened only by the cooling system commissioning person-
nel and it must be installed immediately, as air humidity
can damage the filter dryer
Commissioning
Commissioning may be carried out only by a qualified
cooling and refrigeration specialist company.
Maintenance
Service and maintenance should be carried out in accord-
anse to the manufacturers instructions and national regu-
lations.
The company reserves the right to make design changes without prior notice.