Safety, Environmental and Regulatory Information
3.6

Internal Battery

The Ewon Flexy 205 contains a CR2032 battery. This battery is used to maintain the real time
clock up-to-date even when the unit is not powered.
Here is a list of risks and recommendations regarding the battery:
Risk of explosion if the battery is replaced by an incorrect type. The battery is not intended
to be replaced by the consumer: the product shall be returned to the manufacturer for
replacement.
Do not ingest battery, chemical burn hazard.
Keep new and used batteries away from children.
If the cell battery is swallowed, it can cause several internal burns in just 2 hours and can
lead to death.
If the equipment's enclosure do not close securely, stop using the product and keep it away
from children.
If you think batteries might have been swallowed or placed inside any part of the body, seek
immediate medical attention.
3.7
Field Implementation & Environmental Conditions
3.7.1
Ingress Protection
The Ewon Flexy 205 has an IP20 protection grade. Therefore, the Ewon Flexy 205 is NOT suited
for outdoor mounting.
It has to be integrated in an electrical cabinet, protected from excessive heat, humidity and dust.
Do not push any sharp object into the air vents or openings of the equipment.
3.7.2
Mounting Recommendations
The product is intended to be mounted vertically, label on the right side.
The normal mounting position of the Ewon Flexy 205 is wall mounted on a horizontal
Omega type DIN-rail (EN
Mounting the unit on DIN-rail
Pull the slide lock (located at the bottom of the back-side of the unit) downwards and
present the unit in front of the DIN rail. Tilt the Ewon upwards in order to hang it on the
upper edge of the DIN rail by its hook. Gently tilt the unit downwards until it finds its
original position. Pull the slide lock upwards to fix and lock the unit on the DIN rail.
Removing the unit from DIN-rail
Release the unit by pulling the slide lock downwards while gently tilting the unit upwards.
Free the unit by unhooking it from the upper rail edge.
Flexy 205 Installation Guide
Risk of explosion if the battery is replaced by an incorrect type. The battery is not
intended to be replaced by the consumer: the product shall be returned to the
manufacturer for replacement.
50022).
9 (32)