Turn the Upper Line knob (right) to select High Flow Delay.
3.
HIGH FLOW DELAY
050 GPM
Turn the Lower Line knob to adjust the delay minutes (1–6).
4.

Setting the No Flow Threshold

Note: To prevent a false alert response, the No Flow threshold should be
set 10–15% lower than the expected flow in any program configuration.
Turn the Upper Line knob (right) to select No Flow Threshold.
1.
NO FLOW THRESHOLD
005 GPM
The default threshold will be displayed. To adjust, turn the Lower
2.
Line knob. The value is adjustable from Off –30 in one-GPM
increments, or 30–995 in five-GPM increments.
3.
Turn the Upper Line knob (right) to select No Flow Delay.
NO FLOW DELAY
005 GPM
Turn the Lower Line knob to adjust the delay period (1–6 minutes).
4.
3 Minutes
3 Minutes
3 Minutes
51