Installation
6
Installation
6.1
Measures before installation
6.2
Installation position
03/19
The FlowTimer+ Protect must be installed in the piping
system by a trained technician according to the installation
instructions.
If the operating pressure is greater than 10 bar, a pressure
reducer must be installed upstream of the FlowTimer+ Protect.
If no filter has been installed in the cold water inlet of the entire
system, it should now be retrofitted to protect the valve from
contamination.
Existing KFR valves, non-return valves or non-return valves
must be tested for function and tightness and replaced if
necessary.
The FlowTimer+ Protect is always installed upstream of the
pipeline section to be shut off and the consumer.
FlowTimer+ Protect Set
12