5.4.2
Machine frame mounting feet (special design)
For terminal boxes mounted at the NDE (option H08), dimension C can deviate from IS1231.
For motors with double or triple holes at the NDE, maintain the foot mounting dimensions as specified in standard IS1231.
6

Electrical connection

Observe the following when carrying out any work on the machine:
● Comply with the general safety instructions (Page 1)
● Comply with the applicable national and sector-specific regulations.
● When using the machine within the European Union, comply with the specifications laid down in EN 50110-1 regarding
safe operation of electrical equipment.
6.1

Connecting the machine

DANGER
Hazardous voltages
Death, injury or material damage can occur. Note the following safety information before connecting-up the
machine:
Only qualified and trained personnel should carry out work on the machine while it is stationary.
Disconnect the machine from the power supply and take measures to prevent it being reconnected. This
also applies to auxiliary circuits.
Check that the machine really is in a no-voltage condition.
Establish a safe protective conductor connection before starting any work.
If the incoming power supply system displays any deviations from the rated values in terms of voltage,
frequency, curve form or symmetry, such deviations will increase the temperature and influence
electromagnetic compatibility.
Operating the machine on a line supply system with a non-grounded neutral point is only permitted over
short time intervals that occur rarely, e.g. the time leading to a fault being eliminated (ground fault of a
cable, EN 60034-1).
6.1.1
Direction of rotation
The standard motors are suitable for clockwise and counter-clockwise rotation.
For defined directions of rotation (direction of rotation arrow), appropriately connect the line power cables.
● If you connect the line cables with phase sequence L1, L2, L3 at U, V, W or according to NEMA at T
machine rotates in the clockwise direction.
● If you interchange two connections, e.g. L1, L2, L3 at V, U, W or according to NEMA at T
rotates counter-clockwise.
Clockwise rotation
Counter-clockwise
rotation
Direction of rotation of the motor when looking at DE
18
According to IEC
U V W
V U W
T
T
, then the
1
2
3
T
T
, then the machine
2
1
3
According to NEMA
T
T
T
1
2
3
T
T
T
2
1
3
A5E36065207, 04/2018
1LE7