1MRK 514 026-UUS F
PosNo
1a, 1b
2
3
5.3.3
Wall mounting
5.3.3.1
Overview
All case sizes, 1/2 x 19", 3/4 x 19", and 1/1 x 19", can be wall mounted. It is also possible to mount
the IED on a panel or in a cubicle.
5.3.3.2
Mounting procedure for wall mounting
Figure 5:
5.3.3.3
How to reach the rear side of the IED
The IED can be equipped with a rear protection cover recommended to be used with this type of
mounting. See figure 6.
To reach the rear side of the IED, a free space of 3.2 inches is required on the unhinged side.
670 series
Installation manual
Description
Mounting angles, can be mounted either
to the left or the right side of the case
Screw
Washer
Use only the screws included in the mounting kit when mounting the plates and the
angles on the IED. Screws with wrong dimension may damage the PCBs inside the
IED.
If fiber cables are bent too much, the signal can be weakened. Wall mounting is
therefore not recommended for any communication modules with fiber
connection.
Wall mounting details.
Quantity
Type
2
-
8
M4x6
8
M4x6
Section 5
Mounting
IP10316-1 v1
M11973-3 v7
M11949-2 v3
M11941-2 v5
23