Caution Signs - ABB Relion 670 Series Installation Manual

Version 2.2 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 2
Safety information
2.3

Caution signs

12
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
Never connect or disconnect a wire and/or a connector to or from a IED during
normal operation. Hazardous voltages and currents are present that may be lethal.
Operation may be disrupted and IED and measuring circuitry may be damaged.
Dangerous voltages can occur on the connectors, even though the auxiliary voltage
has been disconnected.
Always connect the IED to protective ground, regardless of the operating
conditions. This also applies to special occasions such as bench testing,
demonstrations and off-site configuration. This is class 1 equipment that shall be
grounded.
Never disconnect the secondary connection of current transformer circuit without
short-circuiting the transformer's secondary winding. Operating a current
transformer with the secondary winding open will cause a massive potential build-
up that may damage the transformer and may cause injuries to humans.
Never remove any screw from a powered IED or from a IED connected to powered
circuitry. Potentially lethal voltages and currents are present.
Take adequate measures to protect the eyes. Never look into the laser beam.
The IED with accessories should be mounted in a cubicle in a restricted access area
within a power station, substation or industrial or retail environment.
Whenever changes are made in the IED, measures should be taken to avoid
inadvertent tripping.
1MRK 514 026-UUS F
M2364-2 v1
M2370-2 v1
GUID-BEDD698E-356C-4CF9-9DAE-64DB3CEADEAD v1
M2369-2 v3
M2367-2 v1
M2372-2 v1
SEMOD168311-3 v1
GUID-11CCF92B-E9E7-409C-84D0-DFDEA1DCBE85 v2
IP1503-1 v1
GUID-5D1412B8-8F9D-4D39-B6D1-60FB35797FD0 v2
670 series
Installation manual