Frico Elektra C Series Mounting And Assembly Instruction page 11

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 11
Application area
The fan heater is approved for damp and
wet conditions and can be used in corrosive
environments, like car washes and other tough
conditions. For both fixed installation and
portable use.
The fan heater should be installed for easy
maintenance and inspection. For portable use,
mount a suitable terminal with appropriate
protection class. The fan heater is tested and
approved according to the EMC- and SEMKO
regulations and is CE compliant.
Protection class: IP65.
The casing is made of acid resistant stainless
steel SS2348, heating rods in stainless steel
SS2320, brackets and front grille in powder coated
stainless steel.
Operation
The fan is running constantly unless the output
selector is set in 0 position. The heat output is
controlled by the built in thermostat (+5 – 35°C)
or with an external thermostat (KRT1900).
The on/off mode, and half or full heat output
can be controlled with the output selector on the
unit or with an external control panel (ELSRT/
ELSRT4) mounted on the wall for easy access.
External control box or thermostat are ordered
separately.
Off
Only fan
Fan + half output
Fan + full output
Mounting
Elektra C can be mounted permanently on the
wall or be used as a portable fan heater.
Wall mounting
The fan heater must not be placed immediately or
directly below or in front of a wall socket. Remove
the plastic feet on the brackets.
1. Drill four holes in the wall with a c-c distance
according to fig. 2 on page 2. Fit the screws in
the upper two holes.
2. Attach the brackets on to the fan heater
according to fig. 3 on page 3 with three screws
on each side.
3. Hang the heater by using the keyholes in the
bracket and lock with the two lower screws.
Note! The minimum distances according to fig. 1
on page 2.
Elektra C
Mounting and assembly instruction
Portable use
Mount the enclosed brackets according fig. 4 on
page 3.
Electrical installation
The electrical installation should be carried out
by a qualified electrician in conformity with
prevailing regulations. The appliance should be
preceded by an omnipolar switch with at least
3 mm breaking gap.
Use the knock-outs on the back of the appliance
for installation of the external devices. Cable-
glands used must guarantee the protection class
requirements.
Overheating
Note! Opening the heater cover should only be
done by a qualified installer.
The heater is equipped with an overheat
protection with manual reset. If it is released due
to overheating, reset as follows:
• Disconnect the power supply with the omnipolar
switch.
• Investigate the matter and repair the fault.
• Reset cut-out by opening the lid and pressing
the red button until a click is heard.
• Put on the lid and make sure that the
screws are tightened to ensure full protection.
If the fault continues, please contact a qualified
technician.
Care and maintenance
Elektra C should only be switched off using
the output selector on the unit or the external
control panel ELSRT/ELSRT4. A heating element
is placed inside the junction box and prevents
dampness even when the appliance is switched
off. See wiring diagrams, component 7.
Note! Opening the heater cover should only be
done by a qualified installer. Always disconnect
the power supply before opening the cover or
doing any maintenance work.
The appliance should be cleaned regularly both
inside and outside, to prevent overheating and
risk of fire but also to guarantee long life of the
heater.
Note! To keep the protection class it is very
important to tighten the screws properly when
the lid is put back again after installation or
maintenance. When the screw has reached the
rubber gasket, continue another 2 1/2 turns.
GB