Rexroth IndraDrive
5
Transport and Storage
5.1
Transporting the Devices
Conditions
5.2
Storing the Devices
Conditions
In Case of Long Storage Periods
DOK-INDRV*-HMV-*******-PR01-EN-P
temperature
relative humidity
absolute humidity
moisture condensation
icing
Shock check not in operation
according to EN 60068-2-27
Fig. 5-1: Conditions for transport
temperature
relative humidity
absolute humidity
moisture condensation
icing
Fig. 5-2: Conditions for storage
The power supply units contain sensitive electrolytic capacitors.
Therefore, in the case of long storage periods, operate the power supply
units once a year for at least 1 hour with power on (DC bus voltage must
be applied).
Transport and Storage
-25 ... 70 °C
5 ... 95%;
climatic category 2K3
3
1 ... 60 g/m
climatic category 2K3
not allowed
not allowed
Halve sine in 3 axis:
10g / 11ms
-25 ... 55 °C
5 ... 95%;
climatic category 1K3
3
1 ... 29 g/m
climatic category 1K3
not allowed
not allowed
5-1