A Technical Specifications; Environmental Specifications; Electrical Specifications - Huawei TP48200A-HX09A1 User Manual

Table of Contents

Advertisement

TP48200A-HX09A1 and TBC300A-DCA5 Telecom
Power
User Manual
A.1 Environmental Specifications
Table A-1 Environmental specifications
Item
Operating temperature
Transportation temperature
Storage temperature
Operating humidity
Transportation humidity
Storage humidity
Altitude
A.2 Electrical Specifications
Table A-2 Electrical specifications
Item
Specifications
AC input
AC input system and input voltage
Input frequency
Power factor
Issue 03 (2019-11-15)
A
Technical Specifications
Specifications
-10° C to +45° C with 1120 W/m
-40° C to +70° C
-40° C to +70° C
5%–95% RH (non-condensing)
5%–95% RH (non-condensing)
5%–95% RH (non-condensing)
0-4000 m
When the altitude ranges from 2000 m to 4000 m, the operating
temperature decreases by 1° C for each additional 200 m.
Copyright © Huawei Technologies Co., Ltd.

A Technical Specifications

2
solar radiation
220 V AC single-phase: 85-300 V AC
(phase voltage)
220/380 V AC three-phase, four-wire:
85-300 V AC (phase voltage)
Frequency range: 45-66 Hz; nominal
frequency: 50 Hz or 60 Hz
≥ 0.99 (load percentage ≥ 50%)
80

Advertisement

Table of Contents
loading

This manual is also suitable for:

Telecom power tbc300a-dca5

Table of Contents