TP48200A-HX09A1 and TBC300A-DCA5 Telecom
Power
User Manual
Port Type
Issue 03 (2019-11-15)
Silk Screen
Associated Alarm
Default mode (Close: alarm; Open: normal) can be modified
as required.
ALM7
Reports alarms for door status (including the power cabinet
and battery cabinet).
Default mode (Close: alarm; Open: normal) can be modified
as required.
Reports alarms for battery cabinet heater faults, fan faults
ALM8
(including the power cabinet and battery cabinet), and high
temperatures detected by the temperature control unit (TCU)
in the power cabinet.
Default mode (Close: alarm; Open: normal) can be modified
as required.
Copyright © Huawei Technologies Co., Ltd.
C Associations between Alarms and Dry Contacts on the
UIM
86