Figure 3-8 Rectifier panel
(1) Run indicator
Indicator Description
Table 3-3 Indicator description
Indicator
Color
Run indicator
Green
Alarm indicator
Yellow
Fault indicator
Red
Issue 03 (2019-11-15)
(2) Alarm indicator
Status
Steady on
Off
Off
Steady on
Off
Steady on
Blinking at 4 Hz
Copyright © Huawei Technologies Co., Ltd.
Description
The rectifier provides output properly.
The rectifier provides no output.
No alarm is generated.
The rectifier generates an alarm due to ambient
overtemperature.
The rectifier generates an alarm for shutdown due to
ambient overtemperature or undertemperature.
The rectifier protects against AC input overvoltage
or undervoltage.
The rectifier is hibernating.
The rectifier is running properly.
The rectifier locks out due to output overvoltage.
The rectifier has no output due to an internal fault.
The rectifier is loading an application program.