Vertiv Liebert DSE Packaged Series Installer/User Manual page 87

400 kw to 500 kw
Table of Contents

Advertisement

LIEBERT DSE PACKAGED SOLUTION
Rear
of
Unit
1"
25mm
Typ.
All Sides
24"
610mm
Typ. (6) Plcs.
Both Ends
5 7/8"
149mm
Typ.
Both Ends
Notes:
1. Underside of unit. Coil and fan removed for clarity.
2. Quantity of 36 mounting holes of 5/8" diameter provided for anchorage. Mounting requirement details such as brand, type, embedment depth,
concrete strength, wall bracing, and special inspection must be outlined and approved by the project Structural Engineer of Record.
3. Structural floors and housekeeping pads must be designed and approved by the project Structural Engineer of Record to withstand the seismic
and wind anchor loads as defined on the installation drawings. The installing contractor is responsible for the proper installation of all anchors
and mounting hardware, observing the mounting requirement details outlined by the Engineer of Record.
DPN004188
Page :2 /2
CABINET DIMENSIONAL DATA
400/500kW ROOFTOP UNIT
264"
6706mm
5/8"
O
16mm
Typ. (36) Plcs.
24"
610mm
Typ. (10) Plcs.
Both Sides
Both Sides
155 3/4"
3956mm
12 1/8"
308mm
Typ.
REV : 4
REV DATE : 1/19