Vertiv Liebert DSE Packaged Series Installer/User Manual page 56

400 kw to 500 kw
Table of Contents

Advertisement

11. Install the new cable glands included with the new EC Fan. Torque for the cable glands is:
630 mm and 710 mm fans: 19.5 to 24.75 in-lb (2.2 to 2.8 Nm)
800 mm fans: 32.75 to 38 in-lb (3.7 to 4.3 Nm)
Dispose of the old cable glands once the new glands are installed.
12. Add a compression nut to the wire. Do not tighten the nut.
13. Reconnect the wiring to the proper terminals and verify that the run jumper is in place. See Figure 8.4 on
page 49, and Figure 8.5 on page 50, for wiring details.
The torque for the electrical terminals is 11.5 in-lb (1.3 Nm). Tighten the compression nut to a torque of 22
in-lb (2.5 Nm).
14. With the PCB powered, the board display should read F00.
15. Press the ESC button.
16. Press the UP-arrow button once:
If P- - is displayed, perform step 17.
if P- - is not displayed, perform steps 18 through 46.
17. If P- - is displayed, press the ENT button to enter the P- - Menu.
The P- - Menu allows compact set-up/preparation of the condenser in the factory or in the field. Use the
functions described in Table 8.5 below, to establish a default control configuration for the board.
NOTE: The complete list of P--, C--, and F-- parameters is located inside the lid of the electrical-box panel.
Table 8.5 P-- Menu Items and Definitions
Item
Meaning
ID
Enter
P01
Preparation
Mode
Automatic
VSD
P02
Configuration
Refrigerant
P03
Type
Number
P04
of Circuits
Liebert®
P05
Lee Temp
Option
P06
Condenser
52
Default
Notes
Setting this value to '1' enables preparation mode. All other 'P—'menu items are disabled until this value is '1'. Note
that control operations may be affected during preparation mode, therefore the cooling unit should be off. Setting this
0
value back to '0' creates new default values based upon selections in this menu. After default values are established,
the board exits preparation mode and reboots.
This item should only be used to address the VSDs for the unit. The value entered indicates the model of the VSD:
1 – EBM
2 – Ziehl-Abegg
1
3 – Fans Tech
All fans must be the same model to use this parameter. When ENT is pressed, the board will operate and power
contactors for the VSDs and assign ModBus addresses. This procedure may take up to 5 minutes to complete.
1 = R22
2
2 = R407C
3 = R410A
1 = Single Circuit
1
2 = Dual Circuit
0 = No Lee Temp installed
0
1 = Liebert® Lee-Temp installed
1
0 = Small
Vertiv | DSE Packaged Solution Installer/User Guide

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Liebert dse packaged 400Liebert dse packaged 500

Table of Contents