1. Underside of unit. Coil and fan removed for clarity.
2. Quantity of 32 mounting holes of 5/8" diameter provided for anchorage. Mounting requirement details such as brand, type, embedment depth, concrete strength,
wall bracing, and special inspection must be outlined and approved by the project Structural Engineer of Record.
3. Structural floors and housekeeping pads must be designed and approved by the project Structural Engineer of Record to withstand the seismic and wind
anchor loads as defined on the installation drawings. The installing contractor is responsible for the proper installation of all anchors and mounting hardware,
observing the mounting requirement details outlined by the Engineer of Record.