Pentair FLECK 5812 XTR Installer Manual page 69

Hide thumbs Also See for FLECK 5812 XTR:
Table of Contents

Advertisement

Screen name
Parameters
Day override
Time driven
Regeneration
time
Valve
Reserve
Volume
override
Regeneration
Regeneration
flow
Ref. MKT-IM-019 / E - 14.10.2019
Installer Manual Fleck 5812 - XTR - Programming
Values
OFF - 1 - 99 days
Mandatory for timeclock systems.
Available to be programmed for all
regeneration types.
4, 8, 12, 16 and 20
4 to 20 hours setting available only for the
hours
timeclock systems
Required for time clock and delayed
regeneration types. Set for immediate
regeneration types only when a day override is
12/24 hours clock
also set.
Not available for timeclock system if day
override is set from 4 to 20 hours.
Only available when softener meter delayed
regeneration type is selected.
Fixed %
Selecting fixed % or fixed volume will display
Fixed volume
additional configuration options.
Weekly reserve
Weekly reserve is calculated based on
Variable reserve
average day of week's water usage.
Variable reserve is calculated based on
previous day's water usage.
1 to 999 999 999
Only displayed when regeneration type is filter
gallons/liters
immediate or filter delayed.
Cycle steps on the home screen and during
regeneration will change to reflect the cycle
steps and order in the selected regeneration
flow.
Downflow
Additional regeneration screen parameters
Downflow 2x BW
are dependent upon selected regeneration
Upflow
flow. Not all parameters will be displayed,
Custom Downflow
depending of the selected regeneration flow.
Custom Upflow
Custom upflow, downflow and filter allows for
Variable Refill
up to 20 programmable cycle steps.
Filter
Variable refill calculates refill time based on
Custom Filter
salt dosage, media volume, and BLFC Size,
and it is not possible to change it.
Time per cycle step can be programmed for
all other regenerant flow options.
Notes
69 / 132

Advertisement

Table of Contents
loading

Table of Contents