Basic Safety Instructions - Delta M88H_121 ST Quick Installation Manual

Solar inverter
Table of Contents

Advertisement

Basic safety instructions

Safety instructions for all M88H
WARNING
Electric shock
When the cover is removed from the wiring box,
this exposes voltage-carrying parts and protec-
tion conforming to IP65 is no longer guaranteed.
► Remove the cover only when absolutely
necessary.
► Do not remove the cover if water or dirt
might enter the inverter.
► After work is completed, ensure that the
cover is properly replaced and screwed in.
Check that the cover is properly sealed.
NOTICE
Incorrectly dimensioned solar system.
A solar system of the wrong size may cause
damage to the inverter.
► When calculating the module string, always
pay attention to technical data of the inverter
(input voltage range, maximum current
and maximum input power); see chapter
"Technical Data."
To comply with the IEC 62109-5.3.3 safety requirements
and avoid injury or material damage, the inverter must be
installed and operated in accordance with the safety and
operating instructions set out in this manual. Delta Electro-
nics is not responsible for damage resulting from failure to
follow the safety and operating instructions set out in this
manual.
The inverter may be installed and commissioned only by
installers who have been trained and certified for the instal-
lation and operation of mains-based solar inverters.
All repair work on the inverter must be carried out by Delta
Electronics. Otherwise, the warranty will be void.
Warning instructions and warning symbols attached to the
inverter by Delta Electronics must not be removed.
The inverter has a high leakage current value. The groun-
ding cable must be connected before commencing opera-
tion.
Do not disconnect any cables while the inverter is under
load due to risk of a fault arc.
To prevent damage due to lightning strikes, follow the provi-
sions that apply in your country.
The surface of the inverter can get very hot during operati-
on. Wear safety gloves when you touch the inverter (apart
from at the display).
The inverter is very heavy. For lifting and moving use a me-
chanical lifting device (e.g. a crane or hoist). At least three
persons are required for manual hoisting and moving.
Only equipment in accordance with SELV (EN 60950) may
be connected to the RS485 interfaces.
All connections must be sufficiently insulated in order to
ensure the IP65 degree of protection. Unused connections
must be closed using cover caps.
4
Safety instructions for the M88H_121 (ST)
DANGER
DANGER
Quick installation guide for solar inverter M88H RPI883M121300 RPI883M122300 EU V1 EN 5017414200_00 2019-11-07
Electric shock
Potentially fatal voltages are present at the
inverter during operation. When the inverter
is disconnected from all power sources, this
voltage remains in the inverter for up to 100
seconds.
Therefore, always carry out the following steps
before working on the inverter:
1. Disconnect the inverter from all AC and DC
voltage sources and make sure that none
of the connections can be accidentally
restored.
2. Wait at least 100 seconds until the internal
capacitors have discharged.
Electric shock
Potentially fatal voltages are present at the
inverter DC connections. When light falls on the
solar modules, they immediately start to genera-
te electricity. This also happens when light does
not fall directly on the solar modules.
► Never disconnect the inverter from the solar
modules when it is under load.
► Disconnect the connection to the mains so
that the inverter cannot supply energy to the
mains.
► Disconnect the inverter from all AC and DC
voltage sources. Ensure that none of the
connections can be restored accidentally.
► Ensure that the DC cables cannot be
touched accidentally.

Advertisement

Table of Contents
loading

This manual is also suitable for:

M88h_122 cf

Table of Contents