Setting An Address And Installation Option Of Ahu Kit; The Procedure Of Option Setting; Entering Mode For Option Setting - Samsung MCM-D201N Installation Manual

Ahu kit
Table of Contents

Advertisement

Setting an address and installation option of AHU KIT

Set the address of an AHU KIT and installation option with remote controller options. Set each option separately since
you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to set twice
when setting the address of an AHU KIT and installation option.
The reception part of a remote controller is built in the AHU KIT PBA.

The procedure of option setting

Entering mode for
option setting
High Temp Button
Low Temp Button
Step 1. Entering mode for option setting
1. Remove batteries from the remote controller.
2. While pressing the button of high temp and low temp at the same time, insert the batteries.
3. Check if you have entered the option setting status.
Step 2. The procedure of option setting
After entering the option setting status, select the option as listed below.
• Option setting is available from SEG1 to SEG 24
• SEG1, SEG7, SEG13, and SEG19 are not set as page option.
CAUTION
• Set the SEG2~SEG6, and SEG8~SEG12 as ON status and SEG14~18, and SEG20~24 as OFF status.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
0
X
X
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
2
X
X
X
X
X
1
X
X
X
3
Option setting mode
X
X
X
X
X
X
X
X
X
X
Mode change
High Fan Button
Low Fan Button
On(SEG1~12) Off(SEG13~24)
19