Samsung MCM-D201N Installation Manual page 26

Ahu kit
Table of Contents

Advertisement

Setting an address and installation option of AHU KIT
Option
SEG7
(When setting SEG3)
Explanation
PAGE
Standard for mode change
Cooling → Heating mode
Remote
Controller
Display
Indication Details Indication
0
1
2
Indication
3
and Details
1
4
5
6
7
Option
SEG13
Explanation
2
Option
SEG19
Explanation
PAGE
HP setting
Remote
Controller
Display
Indication Details Indication
0
1
Indication
and Details
3)
2
3
4
1) Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.
For example, When the indoor unit is installed 40 m(131.23 ft) higher than the indoor unit installed at the lowest place, select the option "1".
2) Distance : The difference between the pipe length of the indoor unit istalled at the farthest place from an outdoor unit and the pipe length of the corresponding indoor unit from an outdoor
unit. For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40 m(131.23 ft) away from an outdoor unit, select the option "2". (100 m(328 ft) -
40 m(131.23 ft) = 60 m(196.85 ft))
3) Regardless of the AHU KIT HP setting, one indoor unit will be recognized. Therefore, be careful when setting the number of the indoor unit installation with an outdoor unit.
26
SEG8
SEG9
(When setting SEG3)
Time required for mode
change
Details
Indication
Details
1
0
5 min.
1.5
1
7 min.
2
2
9 min.
2.5
3
11 min.
3
4
13 min.
3.5
5
15 min.
4
6
20 min.
4.5
7
30 min.
SEG14
SEG15
-
-
SEG20
SEG21
Fan Feedback
Details
Indication
Details
Default
0
Disuse
(10 HP)
10 HP
1
Use
20 HP
30 HP
40 HP
SEG10
Compensation option for Long
pipe or height diffference between
indoor units
Indication
Details
0
Use default value
1)
1) Height difference
is
more than 30 m or
1
2)
2) Distance
is longer
than 110 m
1)
1) Height difference
is
15~30 m or
2
2)
2) Distance
is
50~110 m
SEG16
Simple BMS temperature
-
Indication
SEG22
Defrost signal
Skip the prevention of cold air
Indication
Details
Indication
0
Disuse
0
1
Use
1
SEG11
SEG17
control
Details
Room
0
temperature
Discharge
1
temperature
SEG23
Details
Indication
Sharing the room and discharge
Disuse
0
temperature value of a master
indoor unit
Master indoor unit
- Room temperature : PT1000 Ω
Use
1
- Discharge temperature :
4~20 mA
Master indoor unit
- Room temperature : 4~20 mA
2
- Discharge temperature :
PT1000 Ω
Master indoor unit
- Room temperature : a wired
3
remote controller' s sensor
- Discharge temperature :
4~20 mA
SEG12
SEG18
-
SEG24
Sensor
Details