Flexputs™ I/O Circuits
3.5.2 Releasing Operations
Approved releasing solenoids are list in Table 3.8. Do not mix cross alarming zones with smoke verification zones. There must be at
least two automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the linear spacing in accordance
with NFPA 72.
Manufacturer
Asco

Class B Notification Wiring

You must use an appliance from the list of compatible appliances in Appendix A.
To install a Class B notification appliance circuit:
1.
Wire Class B Notification appliances as shown in Figure 3.12.
2.
Configure the circuit through programming.

Class A Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1.
Wire the Class A notification appliances as shown in Figure 3.13.
5895XL Manual - P/N 151142-L8:L 08/09/2017
Table 3.8 Approved Releasing Solenoids
Part Number
T8210A107
8210G207
UL Listed EOL
4.7 k
Figure 3.12 Class B Notification Appliance Circuit Wiring
Rating
Current
24 VDC
3A max
24 VDC
3A max
Notification Wiring
Supervised
Power Limited
Regulated
Hardware Installation
Freq
0 Hz
0 Hz
alarm polarity shown.