Installation; Mechanical Installation; Electrical Installation; Connecting Communication Links - Bodet KELIO VISIO Instructions Manual

Table of Contents

Advertisement

4.

INSTALLATION

4.1 Mechanical installation

-
The terminal is designed for indoor installation only.
-
Select premises with low temperature variations and far from any electromagnetic
interference sources (contactors, motors, other badge swipe readers, etc.).
-
Open the terminal with the key [A].
-
Remove connector [J] and unclip the front panel of the terminal.
-
Remove the the protection plate [C] by loosening the 2 screws and by sliding it upwards.
-
Fasten the back of the terminal where selected, using the 4 dowel pins and 4 screws
supplied.

4.2 Electrical installation

-
With the system de-energized, connect the contacts of the relay (230 V, 4A
block [B1].
-
For mains supply: After de-energizing the relevant circuit-breaker / disconnecting switch,
connect the 230 Volt ±10% 50 Hz mains supply to the concentrator block [B2] (1.5 to
2
2.5 mm
cross-section phase, neutral and earth wire, bare on a 5 mm length).
-
For low voltage power supply: Connect a 12 V
concentrator block [B4]. Should the external power supply be equipped with an off-mains
operating battery, if necessary, connect the "mains supply" signal (12 V
0 V
= no mains supply) to the upper part of the concentrator block [B4].
DC
-
Connect the low voltage power cord of concentrator block [B3] to the external electrical
devices (typically BODET Kar readers). The amperage supplied by the terminal on this
concentrator block is limited to 200 mA. The maximum voltage supplied is 14.5 V
-
Plug connector [H] from back-up battery [I] to the power-supply board.

4.3 Connecting communication links

-
Connect the France-Inter/DCF radio-synchronization antenna to concentrator block [B5].
The link with the antenna is a 4-20 mA current loop. The current supplied by the terminal is
limited to 50 mA. The maximum voltage supplied is 14.5 V
-
Connect the RS232 line from the PC to the terminal on concentrator block [B6] as shown
on figure below.
Shunter DSR (6)
and DTR (4) to
inhibit
the
flow
control
DB9 connector to the PC
-
Connect the event-driven RS485 line [B7] to the other peripherals such as Kelio Visio
(depending on software configuration).
-
Connect the polling RS485 line [B8] to the peripherals such as attendance boards, Kar
readers, GPS receiver (depending on software configuration).
-
Connect the alarm cable to concentrator block [B9]. The two contacts of the alarm signal
are intended to be connected to an external dry contact (typically the contacts of a fire
alarm system relay).
-
In the event of an RTC modem option, connect the telephone cable to RJ11 connector [D]
or concentrator block [E].
-
Connect the Ethernet 10/100 Mb cable to concentrator block [G].
(11,5 to 15 V
) power supply to the
DC
DC
.
DC
Terminal block F
concentrator
max)
= mains supply,
DC
.
DC