P-55
high total
this parameter will display the 4 highest digits of the 8 digit totalizer used in
pump totalizer or OCM applications. The parameter will also allow the
display to be reset to any value. (F=0000)
P-56
remote totalizer contact control
a momentary closure of the remote totalizer contact occurs once each time
the entered flow or pumped volume has passed
enter option -3 = 0.001
P-57 & P-58 flow sampler control
a momentary closure of the flow sampler contact occurs once each time a
volume of y
enter P-57 (x) = base 10 exponent, -3 to 7 (F=0)
enter P-58 (y) = mantissa, 0.001 to 9999 (F=1.000)
e.g. if P-57
P-59
time sampler control
a momentary closure of the time sampler contact occurs each time the
entered amount of time in hours has elapsed (F=----)
Parameters P-60 through P-67 are used to achieve specialized or custom
calibration.
P-60
full calibration
this provides measurement offset compensation on a full tank. A
measurement offset might occur when parameters 3 and 4 do not exactly
match the tank dimensions referenced for volume conversion. (F=----)
fill tank as much as permissible, but without going into the blanking zone
PL-399
-2 = 0.01
-1 = 0.1
0 = 1 (F)
1 = 10
2 = 100
3 = 1,000
4 = 10,000
5 = 100,000
6 = 1,000,000
7 = 10,000,000
x
10
, as defined by P-57 (x) and P-58 (y), flows or is pumped.
x
= 3 and P-58 = 5, then a sampler contact closure will occur
each time 5 x 10
7 – 11
3
= 5000 units of volume has passed