Hydroranger I; Specifications - Milltronics HydroRanger I Instruction Manual

Programmable level system
Table of Contents

Advertisement

HydroRanger I

Power
Fuse
Range
Accuracy
Resolution
Memory
Display
Operating Temp.
(range in which electronics will
operate within specs, includes
temperature rise above ambient
due to operation in enclosure.)
Ambient Temp.
(range outside of
HydroRanger I enclosure)
OUTPUTS:
transducer drive
analog
PL-399
SECTION II

SPECIFICATIONS

» 100/115/200/230 V
» 50/60 Hz, 15 VA
» optional :
» 1/4 amp MDL Slo-Blo or equivalent
» 0.3 to 10 m (1 to 33 ft.)
» 0.25% of range or 6 mm (0.24"),
whichever is greater
» 0.1% of range or 2 mm (0.08"),
whichever is greater
» EEPROM (non-volatile) no back-up
battery required
» Liquid Crystal Display
4 digits - 18 mm (0.7") high
» -20 to 60 °C
(-5 to 140 °F)
» -20 to 50 °C
(-5 to 122 °F)
» 41 KHz, 400 V peak pulses of 1 mSec. max.
duration at a max. repetition rate of 300 mSec.
» 0 - 20 or 4 - 20 mA
» max. loading: 350 ohms, return to ground
» resolution: 0.1% of range
» optional mA isolator
2 – 1
±
15%, stab selectable
» 12 V DC model, 10 to 18 V DC
» 24 V DC model, 18 to 36 V DC
750 ohms, return to -12 V