Valor LEGEND G4 Series Installation Instructions Manual

Valor LEGEND G4 Series Installation Instructions Manual

Gas conversion kit

Advertisement

Available languages

Available languages

Quick Links

This appliance is certifi ed for use from 0–4500 feet. For
altitudes above 4500 feet, see local codes.
Kit Contents
1 Pilot injector
1 Main burner elbow injector
1 Set of conversion labels
1 Minimum rate by-pass screw
Tools Required
• Wrenches, to disconnect gas line
• Phillips (+) screwdriver, to remove burner module
• Small (jewelers size) fl at blade screwdriver, to set
pressure
• Small fl at blade screwdriver, to release pressure tap
on valve
• Needle nose pliers, to remove by-pass screw
• Hex (Allen) wrench, 4 mm or 5/32", to remove pilot
injector
• Manometer, to set pressure, regulator is integral with valve
Specifi cations
Model
Gas
Altitude (Ft.)*
Input Maximum (Btu/h)
Input Minimum (Btu/h)
Manifold Pressure (in w.c.)
Minimum Supply Pressure
(in w.c.)
Maximum Supply Pressure
(in w.c.)
Main Burner Injector Marking
Pilot Injector Marking
Min. Rate By-Pass Screw
4004566-01
©2014, Miles Industries Ltd.
L
EGEND
Gas Conversion Kit
785NGKV2 / NPKV2
Use with with Valor Models 785J Heaters ONLY
Installation Instructions
785NG
785LPG
Natural
Propane
0-4,500 feet*
33,000
30,000
17,500
19,000
3.2
9.0
5.0
11.0
10.0
14.0
1000
360
51
30
220
125
G4
WARNING
This conversion kit shall be installed by
a qualifi ed service agency in accordance
with the manufacturer's instructions and
all applicable codes and requirements of
the authority having jurisdiction. If the
information in these instructions is not
followed exactly, a fi re, explosion or pro-
duction of carbon monoxide may result
causing property damage, personal injury
or loss of life. The qualifi ed service agency
is responsible for the proper installation of
this kit. The installation is not proper and
complete until the operation of the con-
verted appliance is checked as specifi ed in
the manufacturer's instructions supplied
with the kit.
Use this manual in conjunction with the
installation manual supplied with the
appliance.

Advertisement

loading

Summary of Contents for Valor LEGEND G4 Series

  • Page 1 EGEND Gas Conversion Kit 785NGKV2 / NPKV2 Use with with Valor Models 785J Heaters ONLY Installation Instructions This appliance is certifi ed for use from 0–4500 feet. For WARNING altitudes above 4500 feet, see local codes. This conversion kit shall be installed by Kit Contents a qualifi...
  • Page 2 General Notes Regarding Conversion 6. Using two wrenches disconnect inlet to valve control. The conversion may be done before or after the appliance is installed into the cavity. However, the gas must be connected to set the manifold pressure. Prepare the appliance 1.
  • Page 3 3. Replace with the appropriate pilot injector—see Replace the minimum rate by-pass screw Specifi cations table on page 1. Screw in the new 1. Locate and remove the by-pass screw from the valve injector. and discard. The by-pass screw has a rubber O-ring 4.
  • Page 4 Pry off Increases pressure plastic cap Decreases pressure Designed and Manufactured by / for Miles Industries Ltd. 190–2255 Dollarton Highway, North Vancouver, BC, CANADA V7H 3B1 Tel. 604-984-3496 Fax 604-984-0246 www.valorfi replaces.com © Copyright Miles Industries Ltd., 2014...
  • Page 5 LE PREMIER FOYER À GAZ RADIANT Kit de conversion de gaz 785NGKV2 / NPKV2 Utilisez avec les foyers Valor 785J SEULEMENT Directives d’installation Cet appareil est homologué pour utilisation de 0 à AVERTISSEMENT 4 500 pieds. Pour altitudes au-dessus de 4 500 pieds, consultez la règlementation locale.
  • Page 6 À propos de la conversion 2. Utilisez deux clés pour débrancher la conduite de gaz reliée à la soupape. La conversion d’un gaz à l’autre peut être faite avant ou après l’installation de l’appareil dans la cavité. Cependant, le gaz doit être branché pour régler la pression d’admission.
  • Page 7 3. Enlevez l’injecteur de la veilleuse avec une clé Allen 2. Fixez le brûleur au mécanisme de réglage d’aération et jetez-le. à l’aide des 2 vis enlevées auparavant. d’obturateur d’air 4. Remplacez-le avec l’injecteur approprié—voir le 3. Réinstallez les panneaux intérieurs. tableau Indices siglalétiques à...
  • Page 8 Réglez l’obturateur d’air 2. Fixez un mano-mètre à la Dévissez pour vérifi er connexion de vérifi cation (resserrez après) L’obturateur d’air est situé à l’arrière du brûleur de de pression d’admission Vérifi cation de la céramique. pression d’admission sur la soupape—voir 1.

This manual is also suitable for:

Legend g4 785npkv2Legend g4 785ngkv2