Safety Instructions - Danfoss 175N0128 IP 65 Installation Instructions

Lop connection and set-up vlt drivemotor fcp/fcm 106

Advertisement

Installation Instructions

Safety Instructions

®
Refer to VLT
DriveMotor FCP 106 and FCM 106 Operating
Instructions for detailed information about safety precautions
for installation.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.
1.
Stop the motor.
2.
Disconnect AC mains, permanent magnet type
motors, and remote DC-link supplies, including
battery back-ups, UPS, and DC-link connections to
other frequency converters.
3.
Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in Table 1.1.
Voltage
Power Range
[V]
[kW]
3x400
0.55–7.5
Table 1.1 Discharge Time
1) Power ratings relate to NO, see VLT
Operating Instructions.
2
LOP Connection and Set-up
®
VLT
DriveMotor FCP/FCM 106
Minimum waiting
1)
time
(min)
4
®
DriveMotor FCP 106 and FCM 106
Danfoss A/S © 09/2015 All rights reserved.
Connection to FCP 106 or FCM 106
1.
Connect the LOP as shown in Table 1.2 and
Illustration 1.3.
2.
After completing connections, cut off or isolate
excess wire.
3.
Connect terminal 27 V to +24 V or set
parameter 5-12 Terminal 27 Digital Input to [0] No
operation.
Terminal Dual-speed
operation
18
Purple
19
27
29
12
50
55
Table 1.2 Electrical Connections
Illustration 1.3 LOP Connections to FCP 106 or FCM 106
Dual-mode
Dual-direction
operation
operation
Gray
Brown
Green
Red
Yellow
Blue
MI03L202