Danfoss 175N0128 IP 65 Installation Instructions page 3

Lop connection and set-up vlt drivemotor fcp/fcm 106

Advertisement

Installation Instructions
Set-up
1.
Perform set-up according to Table 1.3.
2.
Use the [+]/[-] keys to set reference.
3.
At power-up, the unit is always in stop mode. The set reference is stored during power down. To set up permanent start
mode, connect terminal 12 to terminal 19 and do not connect purple/gray wire to terminal 12. Permanent start mode
disables the stop function on the LOP.
Function
Default - Dual speed operation
(connect purple or orange wire)
Function 2 - Dual-mode
operation
(connect purple or orange wire)
Function 3 - Dual direction
operation (connect gray wire)
Table 1.3 LOP Operation Mode
1) Set jog speed in parameter 3-11 Jog Speed [Hz]
2) When reset is required, set parameter 5-11 Terminal 19 Digital Input to [1] Reset.
MI03L202
LOP Connection and Set-up
®
VLT
DriveMotor FCP/FCM 106
Settings
No changes to factory setting.
Select the modes of operation in set-ups 1 and 2.
Set parameter 0-10 Active Set-up to [9] Multi Set-up.
Set parameter 5-13 Terminal 29 Digital Input to [23] Set-up
select bit 0.
Set parameter 4-10 Motor Speed Direction to [2] Both
directions.
Set parameter 5-13 Terminal 29 Digital Input to [11] Start
reversing.
Danfoss A/S © 09/2015 All rights reserved.
Key I (Start)
Key II (Start)
Run on set
1)
Run on 5 Hz
reference (+/-)
jog speed
Run with
Run with
set-up 1
set-up 2
Run forward
Run reverse
Key (Stop)
2)
Stop (and reset
- if trip)
2)
Stop (and reset
- if trip)
2)
Stop (and reset
- if trip)
3