Installation And Operation Of The Heat Reclaim With Desuperheater Option - Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

18 - PARTIAL HEAT RECLAIM USING DESUPER-HEATERS (OPTION 49)
18.2 - Installation and operation of the heat
reclaim with desuperheater option
The  30RQS/RQBSY  units  with  the  desuperheater  option  are 
supplied with one heat exchanger per refrigerant circuit.
Typical installation diagram of twin-circuit units with the desuperheater option
Legend
30RQS/RQSY unit components
1 
Evaporator
2 
Compressor
3 
Desuperheater (plate heat exchanger)
4 
Air condenser (coils)
5 
Expansion valve (EXV)
6 
Damage limitation option in case of a fire (relief valve)
7 
Electric heater to protect the desuperheater against frost (not supplied)
8 
Desuperheater insulation (not supplied)
9 
Unit control box 
10  NA
11  Desuperheater water inlet
12  Desuperheater water outlet
13  Evaporator water inlet
14  Evaporator water outlet
15  Unit with desuperheater option without hydraulic module
16  System heat load
17  Border between the 30RQS/RQSY unit and the typical installation
50
30RQS/RQSY unit with desuperheater option without hydfronic module
Border between 30RQS/RQSY unit and the system
Typical installation
During the unit installation the heat reclaim plate heat exchangers 
must be insulated and frost protected, if required.
Please refer to the typical installation diagram below for the main 
components  and  functions  of  the  30RQS/RQSY  units  with  the 
desuperheater option.
Installation components (installation example)
20  Pump (hydraulic circuit of the desuperheater loop)
21  Shut-off valve
22  Desuperheater water flow balancing and control valve
23  Damage limitation option in case of a fire (relief valve)
24  Expansion tank
25  Charge or drain valve
26  Air purge
27  Heat exchange coil or plate heat exchanger
28  Pressure gauge
29  Flow switch
30  Pump (domestic hot water circuit)
31  Three-way valve + controller
32  Filter to protect the pump and the desuperheaters
33  District water supply
34  Domestic hot water outlet