Standard Maintenance; Level 1 Maintenance; Level 2 Maintenance; Level 3 (Or Higher) Maintenance - Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

20 - STANDARD MAINTENANCE

Air  conditioning  equipment  must  be  maintained  by  profes-sional 
technicians,  whilst  routine  checks  can  be  carried  out  locally  by 
specialised technicians. See the standard EN 378-4.
All refrigerant charging, removal and draining operations
must be carried out by a qualified technician and with the
correct material for the unit. Any inappropriate handling can
lead to uncontrolled fluid or pressure leaks.
WARNING: Before doing any work on the machine ensure
that the power is switched off. If a refrigerant circuit is opened,
it must be evacuated, recharged and tested for leaks. Before
any operation on a refrigerant circuit, it is necessary to
remove the complete refrigerant charge from the unit with a
refrigerant charge recovery group.
Simple preventive maintenance will allow you to get the best
performance from your HVAC unit:
• improved cooling performance
• reduced power consumption
• prevention of accidental component failure
• prevention of major time-consuming and costly interventions
• protection of the environment
There are five maintenance levels for HVAC units, as defined by 
the AFNOR X60-010 standard.

20.1 - Level 1 maintenance

See note in chapter 20.3.
Simple procedures, can be carried out by the user on a weekly 
basis:
• Visual inspection for oil traces (sign of a refrigerant leak),
• Air heat exchanger (condenser) cleaning - see chapter 'Air 
heat exchanger - level 1',
• Check  for  removed  protection  devices,  and  badly  closed 
doors/covers,
• Check the unit alarm report when the unit does not work 
(see the 30RB/30RQ Touch Pilot Junior control manual),
• General visual inspection for any signs of deterioration,
• Verify the charge in the sight-glass,
• Check that the water temperature difference between the 
heat exchanger inlet and outlet is correct.

20.2 - Level 2 maintenance

This level requires specific know-how in the electrical, hydraulic 
and mechanical fields. It is possible that these skills are available 
locally:  existence  of  a  maintenance  service,  industrial  site, 
specialised subcontractor.
The frequency of this maintenance level can be monthly or annually 
depending on the verification type.
In  these  conditions,  the  following  maintenance  operations  are 
recommended.
Carry out all level 1 operations, then:
Electrical checks
• At  least  once  a  year  tighten  the  power  circuit  electrical 
connections (see table with tightening torques).
• Check  and  retighten  all  control/command  connections,  if 
required (see table with tightening torques).
• Remove the dust and clean the interior of the control boxes, 
if required.
• Check  the  status  of  the  contactors,  disconnect  switches 
and capacitors.
• Check  the  presence  and  the  condition  of  the  electrical 
protection devices.
• Check the correct operation of all heaters.
• Check that no water has penetrated into the control box.
• For  units  equipped  with  a  variable-speed  drive  regularly 
check  the  cleanliness  of  the  filter  media  to  maintain  the 
correct air flow.
Mechanical checks
• Check the tightening of the fan tower, fan, compressor and 
control box fixing bolts.
Water circuit checks
• Always  take  care  when  working  on  the  water  circuit  to 
ensure that the condenser close by is not damaged.
• Check the water connections.
• Check the expansion tank for signs of excessive corro-sion 
or gas pressure loss and replace it, if necessary.
• Purge  the  water  circuit  (see  chapter  'Water  flow  control 
procedure').
• Clean  the  water  filter  (see  chapter  'Water  flow  control 
procedure').
• Replace the pump fittings after 15000 hours of operation 
with defrost solution or  after 25000 hours of opera-tion with 
water.
• Check the operation of the low water flow rate safety device.
• Check the status of the thermal piping insulation.
• Check  the  concentration  of  the  anti-freeze  protection 
solution (ethylene glycol or propylene glycol).
Refrigerant circuit
• Fully clean the air heat exchangers with a low-pressure jet 
and a bio-degradable cleaner.
• Check  the  unit  operating  parameters  and  compare  them 
with previous values.
• Carry  out  an  oil  contamination  test.  Replace  the  oil,  if 
necessary.
• Check and if necessary re-tighten the Rotalock connections 
in the oil balancing line to the specified torque value.
• Check the operation of the high-pressure switches. Replace 
them if there is a fault.
• Check the fouling of the filter drier. Replace it if necessary.
• Keep and maintain a maintenance sheet, attached to each 
HVAC unit.
All these operations require strict observation of adequate
safety measures: individual protection garments, compliance
with all industry regulations, compliance with applicable local
regulations and using common sense.

20.3 - Level 3 (or higher) maintenance

The  maintenance  at  this  level  requires  specific  skills/approval/
tools and know-how and only the manufacturer, his repre-sentative 
or authorised agent are permitted to carry out these operations. 
These maintenance operations concern for example:
• A major component replacement (compressor, evaporator),
• Any  intervention  on  the  refrigerant  circuit  (handling 
refrigerant),
• Changing  of  parameters  set  at  the  factory  (application 
change),
• Removal or dismantling of the HVAC unit,
• Any intervention due to a missed established maintenance 
operation,
• Any intervention covered by the warranty.
• One to two leak checks per year with a certified leak detector 
and carried out by a qualified person.
To reduce waste, the refrigerant and the oil must be trans-
ferred in accordance with applicable regulations, using
methods that limit refrigerant leaks and pressure drops and
with materials that are suitable for the products.
Any detected leaks must be repaired immediately.
The compressor oil that is recovered during maintenance
contains refrigerant and must be treated accordingly.
Refrigerant under pressure must not be purged to the open
air.
If a refrigerant circuit is opened, plug all openings, if the
operation takes up to one day, or for longer periods charge
the circuit with nitrogen.
NOTE: Any deviation or non-observation of these maintenance
criteria will render the guarantee conditions for the HVAC unit
nul and void, and the manufacturer, Carrier SCS, will no longer
be held responsible.
53

Advertisement

Table of Contents
loading

Table of Contents