Nominal System Water Flow Control; Units Without Hydraulic Module; Units With Hydraulic Module And Fixed-Speed Pump - Carrier AquaSnap Touch Pilot Junior Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

13 - NOMINAL SYSTEM WATER FLOW CONTROL

Refer to the chapter ''Water connections'' for all references
points mentioned in this chapter.
The water circulation pumps of unit range have been designed to 
allow the hydraulic modules to operate at each possible conditions, 
i.e. with chilled water temperature differences at full load from 3 
to 10 K.
This temperature difference required between the water inlet and 
outlet  determines  the  nominal  flow  of  the  system.  Use  the 
specification  provided  while  selecting  the  unit  to  determine  the 
operating conditions of the system. 
In particular, collect the data to be used for the control of the system 
flow rate:
• Units without hydraulic module : the nominal unit pressure 
drop. This is measured with pressure gauges that must be 
(field) installed at the inlet and outlet of the unit (item 21).
• Units  with  fixed  speed  pumps  :  nominal  flow  rate.  The 
pressure of the fluid is measured by sensors at the inlet of 
the pump and outlet of the unit (items 7 and 10).The controls 
then calculate the flow rate associated with this pressure 
difference and display the result on the user interface. (refer 
to unit control manual).
• Units with variable speed pumps : the constant pressure 
differential  control  based  on  readings  at  the  hydraulic 
module inlet and outlet. The buffer tank module option is 
not taken into account.
• Units with variable speed pumps : the control on temperature 
difference measured at the heat exchanger inlet and outlet.
If this information is not available at the start-up of the system, 
contact  the  technical  service  department  responsible  for  the 
installation to obtain them .
These data can be obtained either from the technical document 
with unit performance tables for a Delta T° of 5 K at the evaporator, 
or with the help of the ''Electronic Catalog'' selection program for 
all conditions of Delta T° different from 5 K in the range of 3 to 10 
K. 

13.1 - Units without hydraulic module

13.1.1 - General information
The nominal flow of the unit will be set using a manual valve that 
should  be  installed  on  the  outlet  of  the  unit  (item  19  on  the 
schematic hydraulic circuit). Changing the pressure drop of the 
valve  allows  adjustment  of  the  system  flow  rate  to  achieve  the 
design flow rate.
As  the  total  system  pressure  drop  is  not  known  exactly  at  the 
start-up, it is necessary to adjust the water flow with the control 
valve to obtain the specific flow of the system.
13.1.2 - Procedure for cleaning the hydraulic circuit
• Open the valve completely (item 22).
• Start-up the system pump.
• Read the pressure drop of the plate heat exchanger as the 
difference between the unit inlet and outlet pressures (item 
21).
• Let the pump run for 2 hours consecutively to clean up the 
hydraulic circuit of the system (presence of contaminating 
solids).
• Perform another reading.
• Compare this value to the initial value. A decrease in the 
pressure drop value indicates that the filters in the system 
need to be removed and cleaned. In this case, close the 
Shut-off valves on the water inlet and outlet (item 19) and 
remove then clean the filters (items 20 and 1) after draining 
the hydraulic part of the unit (item 6).
• Remove the air from the circuit (items 5 and 17).
• Repeat until the filter remains clean.
38
13.1.3 - Procedure for controlling the water flow
Once the circuit is cleaned, read the pressures on the pressure 
gauges (water inlet and outlet pressure) determine the pressure 
drop within the unit (plate heat exchanger + internal pipe work).
Compare the value obtained with the design value predicted by 
the selection software.
If  the  pressure  drop  reading  is  above  the  specified  value,  this 
indicates that the flow at the terminals of the unit (and hence in 
the system) is too high. In this case, close the control valve and 
read the new difference in pressure. Repeat as necessary until 
the  pressure  drop  corresponding  to  the  design  flow  rate  is 
achieved.
NOTE: If the network has an excessive pressure drop in
relation to the available static pressure delivered by the
system pump, the nominal water flow cannot be obtained
(lower resulting flow) and the difference in temperature
between the water inlet and outlet of the evaporator will be
increased
To reduce the hydraulic system pressure drop:
• Reduce  the  pressure  drops  of  individual  components 
(bends, level changes, valves etc.) as much as possible
• Use the correct pipe diameter
• Do not extend the piping system.
Example : Unit with specific nominal flow 3.7 l/s
Water flow rate, l/s
Legend
1 
''Unit pressure drop (including internal water piping)/flow rate'' curve
2 
With the valve open the pressure drop read (111 kPa) gives point A on the curve.
A Operating point reached with the valve open.
3 
With the valve open the flow rate achieved is 4.8 l/s: this is too high, and the 
valve must be closed again.
4 
If the valve is partially closed, the pressure drop read (65 kPa) gives point B on 
the curve.
B Operating point reached with the valve partially closed.
5 
Wih the valve partially closed the flow rate achieved is 3.7 l/s: this is the required 
flow rate and the valve is in an adequate position.
13.2 - Units with hydraulic module and fixed-speed
pump
13.2.1 - General information
See chapter ''Units without hydraulic module''.

Advertisement

Table of Contents
loading

Table of Contents