Mechanical; Environmental - AEMC 6472 User Manual

Digital ground resistance and soil resistivity tester
Hide thumbs Also See for 6472:
Table of Contents

Advertisement

Battery Life:
Function
Device off
Voltage Measurement
(2)
3-Poles, 4-Pole
ρ
(4)
V pot.
2 Clamps
GroundFlex
®
(1): Measurements in automatic mode at 25-s intervals - In sweep mode, the number of measurements is
divided by 3 or 4
(2): With R = 1Ω
(3): With RH + RE = 100Ω
(4): With RH + RS-ES = 100Ω

3.5 Mechanical

Dimensions: 10.7 x 9.76 x 5.12" (272 x 248 x 130mm)
Weight: 7 lbs (3.2kg) approx
Case Material: ULV0 Polypropylene
Terminals: 4mm recessed banana jacks
Case Protection: EN 60529 - IP53 (cover closed)
Drop Test: Per EN 61010-1
Vibration Test: Per EN 61557-1

3.6 Environmental

Operating Temperature: 32° to 113°F (0° to 45°C); 0 to 90% RH
Specified Operating Temperature
Storage Temperature: -40° to 158°F (-40° to 70°C); 0 to 90% RH
Altitude: < 3000m
(1): This range corresponds to the one defined by standard EN 61557, for which an operating error including the
quantities of influence is defined. When the device is used outside this range, 1.5%/10°C and 1.5% between
75 and 90% RH must be added to the operating error.
Ground Resistance Tester Model 6472
Power consumed
< 5 mW
1.5 W
4.9 W
4.9 W
(3)
4.9 W
4.9 W
3.7 W
5.5 W
Typical number of measurements
: 0° to 95°F (0° to 35°C); 0 to 75% RH
(1)
(1)
4500
1500
1500
1500
1500
2000
1200
23