AEMC 6472 User Manual page 46

Digital ground resistance and soil resistivity tester
Hide thumbs Also See for 6472:
Table of Contents

Advertisement

3.
Press the 2nd button, then the DISTANCE button. The "hundredths" will blink.
4.
To modify the hundredths (of meters or feet), press the ▲ button until the
desired digit is displayed (0-9).
5.
To select and modify the tens, press the ► button and then the ▲ button until
the desired digit is displayed (0-9).
6.
To select and modify the units and tenths of a unit, press the ► button and
then the ▲ button until the desired digits are displayed (0.0-9.9).
7.
To terminate the programming of distance, press the 2nd button and then the
DISTANCE button.
NOTE: To program distance d, perform the preceding steps.
8.
Start the measurement by pressing the START/STOP button.
9.
To display the measurement parameters, press DISPLAY several times.
The device displays the following parameters:
R
, I
and its frequency, I-Act (I
LOOP
ES
10. Move electrode S (Y) to distance d2, then reprogram the value of d and make
another measurement. Repeat for d3, d4, and d5.
11. Record all of the measurements in order to be able to determine the variation
of the earth potential between points H (Z) and E (X).
44
H
S
A
d
E
H
S
A
=
d
=
E
and its frequency).
ES
Ground Resistance Tester Model 6472
=