Indoor Units Mode Conflict (P5) - Carrier 38MGR Series Service Manual

Multi-zone outdoor unit ductless system, sizes 18, 24, 30, 36, 48
Table of Contents

Advertisement

DIAGNOSIS AND SOLUTION (CONT)

Indoor units mode conflict (P5)

Error Code
Malfunction decision conditions
Supposed Causes
Cooling Mode
Heating Mode
Fan
Off
• No: No mode conflict
38MGR-04SM
P5 (old model) or - (new model)
The indoor units cannot operate the Cooling mode and Heating mode at the same time.
The Heating mode has the priority.
• Suppose indoor unit A is operating under the Cooling or Fan mode, and indoor unit B is set to the
Heating mode, then unit A turns off and unit B operates in the Heating mode.
• Suppose indoor unit A is operating in the Heating mode, and indoor unit B is set to the Cooling or
Fan mode, then unit B enters the Standby mode and unit A will not change its operation.
COOLING MODE
HEATING MODE
No
Yes
No
No
Specifications subject to change without notice.
FAN
Yes
No
No
Yes
Yes
No
No
No
• Yes: Mode conflict
OFF
No
No
No
No
35