Carrier 38MGR Series Service Manual page 33

Multi-zone outdoor unit ductless system, sizes 18, 24, 30, 36, 48
Table of Contents

Advertisement

OUTDOOR UNIT DISPLAY (CONT)
No. of
Display
Presses
0
Normal Display
1
Quantity of indoor units with working connection
2
Outdoor unit running mode code
3
Indoor unit A capacity
4
Indoor unit B capacity
5
Indoor unit C capacity
6
Indoor unit D capacity
7
Indoor unit E capacity
8
Indoor unit A capacity demand code
9
Indoor unit B capacity demand code
10
Indoor unit C capacity demand code
11
Indoor unit D capacity demand code
12
Indoor unit E capacity demand code
13
Outdoor unit amendatory capacity demand code
The frequency corresponding to the total indoor units'
14
amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor control chip
17
Indoor unit A evaporator outlet temperature (T2BA)
18
Indoor unit B evaporator outlet temperature (T2BB)
19
Indoor unit C evaporator outlet temperature (T2BC)
20
Indoor unit D evaporator outlet temperature (T2BD)
21
Indoor unit E evaporator outlet temperature (T2BE)
22
Indoor unit A room temperature (T1A)
23
Indoor unit B room temperature (T1B)
24
Indoor unit C room temperature (T1C)
25
Indoor unit D room temperature (T1D)
26
Indoor unit E room temperature (T1E)
27
Indoor unit A evaporator temperature (T2A)
28
Indoor unit B evaporator temperature (T2B)
29
Indoor unit C evaporator temperature (T2C)
30
Indoor unit D evaporator temperature (T2D)
31
Indoor unit E evaporator temperature (T2E)
32
Condenser pipe temperature (T3)
33
Outdoor ambient temperature (T4)
34
Compressor discharge temperature (TP)
35
AD value of current
36
AD value of voltage
37
EXV open angle for A indoor unit
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
43
Average value of T2
44
Outdoor unit fan motor state
45
The last error or protection code
46
F indoor unit capacity
47
F indoor unit capacity demand code
48
F indoor unit evaporator outlet temperature (T2BF)
49
F indoor unit room temperature (T1F)
50
F indoor unit evaporator temperature (T2F)
51
EXV open angle for F indoor unit
38MGR-04SM
Table 32 — Outdoor PCB
Displays running frequency, running state, or malfunction code
Display
1
2
3
4
Off: 0, Fan only: 1, Cooling: 2, Heating: 3, Forced cooling: 4. Forced defrost: A
The capacity unit is horse power. If the indoor unit is not connected, the digital display shows the
following: "--" (9K:1HP,12K:1.2HP,18K:1.5HP)
Norm code *HP (9K: 1HP,12K: 1.2HP,18K: 1.5HP)
If the temperature is lower than -9 ℃, the digital display shows "-9." If the temperature is higher than 70
℃, the digital display shows "70." If the indoor unit is not connected, the digital display shows: "--"
If the temperature is lower than 0 ℃, the digital display shows "0." If the temperature is higher than 50 ℃,
the digital display shows "50." If the indoor unit is not connected, the digital display shows: "--"
If the temperature is lower than -9 ℃, the digital display shows "-9." If the temperature is higher than 70
℃, the digital display shows "70." If the indoor unit is not connected, the digital display shows: "--"
The display value is between 30–129 ℃. If the temperature is lower than 30 ℃, the digital display shows
"30." If the temperature is higher than 99 ℃, the digital display shows single and double digits. For
example, if the digital display shows "0.5", the compressor discharge temperature is 105 ℃.
The display value is a hex number. For example, the digital display tube shows "Cd", it means AD value
is 205.
Actual data/4. If the value is higher than 99, the digital display shows single and double digits.
For example, if the digital display shows "2.0", the EXV open angle is 120×4=480p.
Bit7
Frequency limit caused by IGBT radiator
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by T5.
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
(Sum T2 value of all indoor units)/(number of indoor units in good connection)
Off: 0, High speed:1, Med speed: 2, Low speed: 3, Breeze:4, Super breeze: 5
00 means No Malfunction and Protection
Specifications subject to change without notice.
Remark
Actual Data
Number of Indoor Units
1
2
3
4
The display value is a hexadecimal
number. For example, the digital
display show 2A, then Bit5=1, Bit3=1,
and Bit1=1.
This means that a frequency limit may
be caused by T4, T3, or the current.
33