4. Installer Information

Installation Guide for Qualified
Personnel
NOTE: This appliance is factory pre-set for Natural Gas
(G25) fuel only as specified on the appliance Data Plate
and shipping label.
Fixing
The GF 400 BF CE2 is designed as a freestanding
appliance and as such does not require additional fixing.
Requirements for Floor Plate
The appliance may stand on a wooden floor. A floor plate
of non-combustible material is required if the appliance
is to be placed on carpet, vinyl, linoleum or other
combustible material. Minimum dimensions of the floor
plate: 686 x 356mm as in fig. 2. Jøtul can supply floor
plates in a variety of colors.
Firewall Requirements
The appliance may be placed directly against a wall made
of combustible material with the clearances specified
in fig. 3. Make sure there is adequate space for the vent
system behind the appliance and for the full height/
length of the pipe.
Position of Appliance
Minimum clearances are as follows: See Figs. 3 - 6.
Clearance from wall to rear of appliance -
Clearance from wall to side of appliance -
Minimum clearance from top of appliance
to register plate -
Minimum clearance from top of appliance
to combustible shelf, -
6
Flue System Installation
Note! During the installation of the vent, it is important
to adhere to national and local regulations that apply.
The system must only be installed with a vent system
approved by Jøtul. Only one single stove may be
connected to the vent system.
The vent system must terminate outdoors.
The vent system is a balanced system: 100% of the
combustion air is supplied from outside the house and
all exhaust gas is returned to outside the house. The
vent pipe is a coaxial pipe in which the combustion air
is supplied through the outer pipe and the exhaust gas
returned through the inner pipe.
Minimum Vent System Clearances to
Combustible Materials
Horizontal Vent Pipe:
From the top of the vent pipe
From the side and bottom of the vent pipe
Vertical Vent Pipe:
From all sides of the vent pipe
Position of Vent Pipe:
Under porch, covered entrance, story or balcony, that
have at least two open sides under the floor
To window or door that can be opened
To permanently closed window, recommended to avoid
condensation on the surface
From vent to roof soffit
100mm
100mm
380mm
Alcove Installation
Maximum Alcove Depth:
600mm
Minimum Alcove Width:
Minimum Ceiling Height from floor:
With Short Legs (6") :
* Alcove dimensions result from specific test
configurations, not stove clearance specifications.
50 mm
25 mm
25 mm
300 mm
300 mm
300 mm
300 mm
63.5 cm*
85.7 cm*
155 cm
150 cm