Bosch Rexroth Servodyn-D Series Maintenance Manuallines page 17

Table of Contents

Advertisement

2–2
Bosch Rexroth AG
Mains connection at the place of installation
Electric Drives
and Controls
Earth connections in the switch cabinet must be designed in the form of a
grid mesh.
The module housing and mounting plate of the switch cabinet must be
earthed. The connection between the line filter and the supply module
should be as short as possible.
The protective earth cross-section must at least correspond to the cross-
section of the line feeder of the supply module.
DANGER
Dangerous shock currents through inappropriate protective earth
connections!
Do not impair protective earth connections by mechanical, chemi-
cal or electro-chemical influences. The connection must be firm
and lasting.
Servodyn-D 1070 066 032 / 03