Akva Lux II VX2, VX2-E, VX3, VX3-E
Instructions for installation and use
Danfoss District Energy

Advertisement

Table of Contents
loading

Summary of Contents for Danfoss Akva Lux II VX Series

  • Page 1 MAKING MODERN LIVING POSSIBLE Akva Lux II VX2, VX2-E, VX3, VX3-E Instructions for installation and use Danfoss District Energy...
  • Page 2: Table Of Contents

    14.2 Wilo-Star-Z NOVA (Circulation set 810.443) ..............................33 15.0 Maintenance ............................................34 15.1 Maintenance plan (recommendations) ................................35 16.0 Troubleshooting ............................................ 36 16.1 Troubleshooting - Heating ...................................... 36 16.2 Troubleshooting - Domestic hot water ................................38 17.0 EC-Declaration of Conformity ......................................40 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 3: Safety Notes

    The substation is made of materials that cannot be disposed of together with household waste. Close all energy sources and disconnect all connection pipes. Disconnect and dismantle the product for disposal in accordance with the applicable local regulations for the disposal of the individual components. Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 4: Diagram - Examples

    5.1 Akva Lux II VX2 Circ. Supply Return Return Supply Bypass Plate heat exchanger, HE, with insulation Controller Danfoss ECL 110/A130 Plate heat exchanger, DHW, with insulation Outdoor sensor Danfoss ESMT Strainer Sensor Danfoss ESMC Non-return valve Danfoss actuator AMV 150 Ball valve...
  • Page 5: Akva Lux Ii Vx2-E

    Return Supply Plate heat exchanger, HE, with insulation Flow switch Plate heat exchanger, DHW , with insulation Safety thermostat Danfoss AT Strainer Sensor pocket for heat meter ½“ Non-return valve Fitting piece for heat meter, 1” x 130 mm Ball valve...
  • Page 6: Akva Lux Ii Vx3

    Circ. Supply Supply Return Return Supply Bypass Plate heat exchanger, HE, with insulation Outdoor sensor Danfoss ESMT Plate heat exchanger, DHW, with insulation Sensor Danfoss ESMC Strainer Danfoss actuator AMV 150 Non-return valve 2-way valve VS2 Ball valve Domestic hot water controller...
  • Page 7: Akva Lux Ii Vx3-E

    Supply Return Return Plate heat exchanger, HE, with insulation Fitting piece for heat meter, 1” x 130 mm Plate heat exchanger, DHW, with insulation Controller Danfoss ECL 310/A376 Strainer Outdoor sensor Danfoss ESMT Non-return valve Sensor Danfoss ESMC Ball valve...
  • Page 8: Main Components

    29 Actuator AMV 150 30 2-way valve VS 2 38 PTC2+P controller 40 Danfoss thermostat for bypass/circulation The substations offer variable connection possibilities, as con- nection of pipes can be established both in the top or in the bottom of the substation.
  • Page 9: Akva Lux Ii Vx2-E

    The circulation set is supplied assembled and electrically wired and ready to mount on the substation as shown on the above photo. Accessories to be ordered separately (mounting on site): White-lacquered steel-sheet cover Art. No. 936.0811 936.0811 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 10: Akva Lux Ii Vx3

    29 Actuator AMV 150 30 2-way valve VS2 38 PTC2+P controller 40 Danfoss thermostat for bypass/circulation The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
  • Page 11: Akva Lux Ii Vx3-E

    The circulation set is supplied assembled and electrically wired and ready to mount on the substation as shown on the above photo. Accessories to be ordered separately (mounting on site): White-lacquered steel-sheet cover Art. No. 936.1541 RES.178 11 11 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 12: Getting Started

    + 5 m (approx. 1.2 - 1.5 bar), - see page 18. 12. Close the fill valve. 13. Subsequently open the ball valve for the DH supply and return flow and heat up the system. 12 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 13: Mounting

    Fig. 6 substation. Fig. 6: Mount plugs in DCW and DHW connection pipes in bottom of substation Please note Akva Lux II VX3-E is supplied with blind plate on the DCW pipe only. 13 13 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 14: Dhw Recirculation Akva Lux Ii Vx2 & Akva Lux Ii Vx3

    The circulation set is supplied assembled and electrically wired and ready to be mounted on the DCW inlet pipe in the bottom of the substation before start up. See photo on page 9 and 11. 14 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 15: Safety Thermostat

    Code no. Heat-conductive compound ~ 5 g 041E0110 Heat-conductive compound ~ 1 kg 041E0111 Danfoss Heating Solutions VDGIA102 © Danfoss 01/2012 If the supply water temperature rises above the thermostat set point (for floor heating 50 °C, for radiator heating 80 °C) the heat pump stops.
  • Page 16: Expansion Vessel

    (not part of the delivery). Establish pipe connection between T-piece and connecting piece on expansion vessel. (Please note that a connection pipe is not part of the delivery). Bracket 16 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 17: Heat Meter, Fitting Piece

    Connect the cable ends to ECL controller in clamps 1 and 2. ECL 310 Connect the cable ends to ECL controller in clamps 29 and 30. Safety valves A discharge outlet from the safety valves must be established in com- pliance with local regulations. 17 17 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 18: Filling, Start-Up

    If the system pressure drops dramatically within a short time, or if you experience that it is necessary often to refill the system, the heating system should be examined for leaks, - this includes checking the factory set pressure of the expansion vessel. 18 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 19: Electrical Connections

    Para Pump, Wilo 230 V a.c., 50 Hz Max. 4.5 Watt Star Z Nova Pump, Wilo Stratos 230 V a.c., 50 Hz Max. 59 Watt Eco Z 19 19 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 20: Description Of Akva Lux Ii Vx Variants

    Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuit is controlled by a Danfoss ECL 110 controller in combination with an electronic actuator. The supply temperature is calculated by the controller on basis of the outdoor temperature.
  • Page 21 DHW temperature control Danfoss PTC2+P controller (1) for DHW. The DHW temperature is adjusted by turning the lever towards “+” (warmer) or “-” (colder). Start by turning the handle clockwise - until stop /until the handle can not be turned anymore.
  • Page 22: Akva Lux Ii Vx2-E (Ecl 310/A266)

    Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuit is controlled by a Danfoss ECL 310 controller in combination with an electronic actuator. The supply temperature is calculated by the controller on basis of the outdoor temperature.
  • Page 23 Emission EN 55014 Environment Normal Installation Installed in any position Accessories Product Code no. Heat-conductive compound ~ 5 g 041E0110 Heat-conductive compound ~ 1 kg 041E0111 Danfoss Heating Solutions VDGIA102 © Danfoss 01/2012 23 23 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 24 (mm) N - 1 (mm) N - 3 (mm) 7369220-2 EI.96.A1.00 © Danfoss 02/02 7369053-0 SIBC VI.HB.C1.00 © Danfoss 5/02 DHW recirculation Substations with electronic control of the domestic hot water circuit are prefabricated for DHW recirculation. The circulation set is supplied assembled, incl. circulation pump and electrically wired and ready to mount on the substation.
  • Page 25: Akva Lux Ii Vx3 (Ecl210/A260)

    Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuits is controlled by a Danfoss ECL 310 controller in combination with electronic actuators. The supply temperature is calculated by the controller on basis of the outdoor temperature.
  • Page 26 (mm) Press and hold the button (on (mm) (mm) the bottom side of the actuator) 7369267-9 SIBC R&D EI.97.Q2.00 © Danfoss 12/01 during manual override. 73691180 DH-SMT/SI VI.KU.N2.1J © Danfoss 01/2008 Circulation pumps, heating circuits See chapter 13 on page 32 for more information about circulation pumps.
  • Page 27 DHW temperature control Danfoss PTC2+P controller (1) for DHW. The DHW temperature is adjusted by turning the lever towards “+” (warmer) or “-” (colder). Start by turning the handle clockwise - until stop /until the handle can not be turned anymore.
  • Page 28: Akva Lux Ii Vx3-E (Ecl310/A376)

    Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuits is controlled by a Danfoss ECL 310 controller in combination with electronic actuators. The supply temperature is calculated by the controller on basis of the outdoor temperature.
  • Page 29 Электроприводы для трехпозиционного регулирования AMV 150 (mm) (mm) Press and hold the button (on (mm) the bottom side of the actuator) EI.97.Q2.00 © Danfoss 12/01 7369267-9 SIBC R&D 73691180 DH-SMT/SI VI.KU.N2.1J © Danfoss 01/2008 during manual override. Control of heating circuit 2...
  • Page 30 Installed in any position Accessories Product Code no. Heat-conductive compound ~ 5 g 041E0110 Heat-conductive compound ~ 1 kg 041E0111 Danfoss Heating Solutions VDGIA102 © Danfoss 01/2012 Remove Set temperature Note! Temperature range for the safety thermostat is 30 - 90 °C.
  • Page 31 AMV 20, AMV 30 + AVQM AMV 20, AMV 30 + VB2 L (mm) (mm) N - 1 (mm) N - 3 (mm) 7369220-2 EI.96.A1.00 © Danfoss 02/02 VI.HB.C1.00 © Danfoss 5/02 7369053-0 SIBC 31 31 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 32: Circulation Pumps - Heating

    It is not only the general safety instructions listed under the main point “safety” that must be adhered to but also the special safety instructions with danger symbols included under the following main points. Installation and operating instructions Wilo-Yonos PARA 02/12 4523676 32 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 33: Circulation Pumps - Domestic Hot Water

    For information about venting of pump etc. please refer to enclosed installation and operating instructions: Wilo-Star-Z NOVA, Installation and operating instructions Wilo-Star-Z NOVA Notice de montage et de mise en service FIN Asennus- ja käyttöohje Monterings- och skötselanvisning DK Monterings- og driftsvejledning 33 33 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 34: Maintenance

    If rinsing with clean water is not sufficient, the exchanger can also be cleaned by circulating a cleaning agent approved by Danfoss (e.g. Radiner Fl cleaning fluid) through the exchanger. Both these cleaning fluids are environmentally friendly and can be disposed off through the standard sewer system.
  • Page 35: Maintenance Plan (Recommendations)

    Please note that the connections may be supplied with EPDM rubber gaskets! Therefore take care not to overstrain the union nuts, as this may result in leaks. The manufacturer accepts no liability for leaks that result from overstrain of union nuts. 35 35 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 36: Troubleshooting

    Defective sensor. Replace sensor. Supply temperature too high Defective controller. The controller does Call in automatic controls manufacturer not react as it is should in accordance or replace controller. with the instructions. 36 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 37 The system is single-pipe. It is extremely important to keep the supply temperature to the radiators as low as ever possible, while maintaining a reasonable level of comfort. 37 37 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 38: Troubleshooting - Domestic Hot Water

    Check if the setting of the controller is tive. correct, - see separate instructions. Non-return valve on the circulation line Replace non-return valve. defective (leads to mixing - the circula- tion water pipes become cold during Variations in temperature tapping). 38 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 39 Poor cooling Calified plate heat exchanger. Clean plate heat exchanger with acid solution or replace plate heat exchanger. Discoloured water (for a longer period) Short-circuiting of plate heat exchanger Replace plate heat exchanger 39 39 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 40: Ec-Declaration Of Conformity

    Telephone +45 87 43 89 43 EC-DECLARATION OF CONFORMITY For CE marking in EU (European Union) Danfoss Redan A/S District Energy DK-8382 Hinnerup Declares under our sole responsibility that below products including all available power and control options: Akva Lux II VX...
  • Page 41 Instructions Akva Lux II VX 41 41 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 42 Instructions Akva Lux II VX 42 DKDHR VI.GP.V2.02 Danfoss District Energy...
  • Page 43 Instructions Akva Lux II VX 43 43 Danfoss District Energy VI.GP.V2.02 DKDHR...
  • Page 44 Danfoss Redan A/S · District Energy · Omega 7, Søften · DK-8382 Hinnerup Tel. +45 87 43 89 43 · Fax: +45 87 43 89 44 · redan@danfoss.com · www.redan.danfoss.dk VI.GP.V2.02 Produced by Danfoss Redan A/S © 05/2013...