The substation is made of materials that cannot be disposed of together with household waste. Close all energy sources and disconnect all connection pipes. Disconnect and dismantle the product for disposal in accordance with the applicable local regulations for the disposal of the individual components. Danfoss District Energy VI.GP.V2.02 DKDHR...
29 Actuator AMV 150 30 2-way valve VS 2 38 PTC2+P controller 40 Danfoss thermostat for bypass/circulation The substations offer variable connection possibilities, as con- nection of pipes can be established both in the top or in the bottom of the substation.
The circulation set is supplied assembled and electrically wired and ready to mount on the substation as shown on the above photo. Accessories to be ordered separately (mounting on site): White-lacquered steel-sheet cover Art. No. 936.0811 936.0811 Danfoss District Energy VI.GP.V2.02 DKDHR...
29 Actuator AMV 150 30 2-way valve VS2 38 PTC2+P controller 40 Danfoss thermostat for bypass/circulation The substations offer variable connection possibilities, as connection of pipes can be established both in the top or in the bottom of the substation.
The circulation set is supplied assembled and electrically wired and ready to mount on the substation as shown on the above photo. Accessories to be ordered separately (mounting on site): White-lacquered steel-sheet cover Art. No. 936.1541 RES.178 11 11 Danfoss District Energy VI.GP.V2.02 DKDHR...
+ 5 m (approx. 1.2 - 1.5 bar), - see page 18. 12. Close the fill valve. 13. Subsequently open the ball valve for the DH supply and return flow and heat up the system. 12 DKDHR VI.GP.V2.02 Danfoss District Energy...
Fig. 6 substation. Fig. 6: Mount plugs in DCW and DHW connection pipes in bottom of substation Please note Akva Lux II VX3-E is supplied with blind plate on the DCW pipe only. 13 13 Danfoss District Energy VI.GP.V2.02 DKDHR...
The circulation set is supplied assembled and electrically wired and ready to be mounted on the DCW inlet pipe in the bottom of the substation before start up. See photo on page 9 and 11. 14 DKDHR VI.GP.V2.02 Danfoss District Energy...
(not part of the delivery). Establish pipe connection between T-piece and connecting piece on expansion vessel. (Please note that a connection pipe is not part of the delivery). Bracket 16 DKDHR VI.GP.V2.02 Danfoss District Energy...
Connect the cable ends to ECL controller in clamps 1 and 2. ECL 310 Connect the cable ends to ECL controller in clamps 29 and 30. Safety valves A discharge outlet from the safety valves must be established in com- pliance with local regulations. 17 17 Danfoss District Energy VI.GP.V2.02 DKDHR...
If the system pressure drops dramatically within a short time, or if you experience that it is necessary often to refill the system, the heating system should be examined for leaks, - this includes checking the factory set pressure of the expansion vessel. 18 DKDHR VI.GP.V2.02 Danfoss District Energy...
Para Pump, Wilo 230 V a.c., 50 Hz Max. 4.5 Watt Star Z Nova Pump, Wilo Stratos 230 V a.c., 50 Hz Max. 59 Watt Eco Z 19 19 Danfoss District Energy VI.GP.V2.02 DKDHR...
Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuit is controlled by a Danfoss ECL 110 controller in combination with an electronic actuator. The supply temperature is calculated by the controller on basis of the outdoor temperature.
Page 21
DHW temperature control Danfoss PTC2+P controller (1) for DHW. The DHW temperature is adjusted by turning the lever towards “+” (warmer) or “-” (colder). Start by turning the handle clockwise - until stop /until the handle can not be turned anymore.
Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuit is controlled by a Danfoss ECL 310 controller in combination with an electronic actuator. The supply temperature is calculated by the controller on basis of the outdoor temperature.
Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuits is controlled by a Danfoss ECL 310 controller in combination with electronic actuators. The supply temperature is calculated by the controller on basis of the outdoor temperature.
Page 27
DHW temperature control Danfoss PTC2+P controller (1) for DHW. The DHW temperature is adjusted by turning the lever towards “+” (warmer) or “-” (colder). Start by turning the handle clockwise - until stop /until the handle can not be turned anymore.
Designed for wall-mounting with connections in top and bottom of substation. The temperature for the heating circuits is controlled by a Danfoss ECL 310 controller in combination with electronic actuators. The supply temperature is calculated by the controller on basis of the outdoor temperature.
It is not only the general safety instructions listed under the main point “safety” that must be adhered to but also the special safety instructions with danger symbols included under the following main points. Installation and operating instructions Wilo-Yonos PARA 02/12 4523676 32 DKDHR VI.GP.V2.02 Danfoss District Energy...
For information about venting of pump etc. please refer to enclosed installation and operating instructions: Wilo-Star-Z NOVA, Installation and operating instructions Wilo-Star-Z NOVA Notice de montage et de mise en service FIN Asennus- ja käyttöohje Monterings- och skötselanvisning DK Monterings- og driftsvejledning 33 33 Danfoss District Energy VI.GP.V2.02 DKDHR...
If rinsing with clean water is not sufficient, the exchanger can also be cleaned by circulating a cleaning agent approved by Danfoss (e.g. Radiner Fl cleaning fluid) through the exchanger. Both these cleaning fluids are environmentally friendly and can be disposed off through the standard sewer system.
Please note that the connections may be supplied with EPDM rubber gaskets! Therefore take care not to overstrain the union nuts, as this may result in leaks. The manufacturer accepts no liability for leaks that result from overstrain of union nuts. 35 35 Danfoss District Energy VI.GP.V2.02 DKDHR...
Defective sensor. Replace sensor. Supply temperature too high Defective controller. The controller does Call in automatic controls manufacturer not react as it is should in accordance or replace controller. with the instructions. 36 DKDHR VI.GP.V2.02 Danfoss District Energy...
Page 37
The system is single-pipe. It is extremely important to keep the supply temperature to the radiators as low as ever possible, while maintaining a reasonable level of comfort. 37 37 Danfoss District Energy VI.GP.V2.02 DKDHR...
Check if the setting of the controller is tive. correct, - see separate instructions. Non-return valve on the circulation line Replace non-return valve. defective (leads to mixing - the circula- tion water pipes become cold during Variations in temperature tapping). 38 DKDHR VI.GP.V2.02 Danfoss District Energy...
Page 39
Poor cooling Calified plate heat exchanger. Clean plate heat exchanger with acid solution or replace plate heat exchanger. Discoloured water (for a longer period) Short-circuiting of plate heat exchanger Replace plate heat exchanger 39 39 Danfoss District Energy VI.GP.V2.02 DKDHR...
Telephone +45 87 43 89 43 EC-DECLARATION OF CONFORMITY For CE marking in EU (European Union) Danfoss Redan A/S District Energy DK-8382 Hinnerup Declares under our sole responsibility that below products including all available power and control options: Akva Lux II VX...
Page 41
Instructions Akva Lux II VX 41 41 Danfoss District Energy VI.GP.V2.02 DKDHR...
Page 42
Instructions Akva Lux II VX 42 DKDHR VI.GP.V2.02 Danfoss District Energy...
Page 43
Instructions Akva Lux II VX 43 43 Danfoss District Energy VI.GP.V2.02 DKDHR...