DCV Set and Max Settings
Adjust settings when an optional IAQ sensor is installed.
The DCV SET potentiometer is factory-set at approxi­
mately 50% of the potentiometer range. Using a standard
1-2000ppm CO
sensor, dampers will start to open when
2
the IAQ sensor reads approximately 1000ppm. Adjust
the DCV SET potentiometer to the approximate setting
specified by the controls contractor. Refer to figure 28.
The DCV MAX potentiometer is factory-set at approxi­
mately 50% of the potentiometer range or 6VDC.
Dampers will open approximately halfway when CO
es above setpoint. Adjust the DCV MAX potentiometer to
the approximate setting specified by the controls con­
tractor. Refer to figure 28.
NOTE - DCV Max must be set higher than economizer mini­
mum position setting for proper demand control ventilation.
Economizer Operation
The occupied time period is determined by the thermostat
or energy management system.
ECONOMIZER OPERATION - OUTDOOR AIR IS SUITABLE FOR FREE COOLING -- FREE COOL LED "ON"
Á Á Á Á Á Á Á Á Á Á
THERMOSTAT DEMAND
Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á
OFF
Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á
G
Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á
Y1
Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á
Y2
* Dampers will open to maintain 55°F (13°C) supply air when an R1 mixed air sensor is installed.
Á Á Á Á Á Á Á Á Á Á
CALCULATE MINIMUM FRESH AIR PERCENTAGE
MIXED AND RETURN AIR TEMPERATURE
-20
-10
0
10
20
-29
-23
-18
-12
-7
-20
-10
0
10
20
-29
-23
-18
-12
-7
OUTDOOR AIR TEMPERATURE
Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
UNOCCUPIED
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
CLOSED
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
CLOSED
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
OPEN*
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
OPEN*
Á Á Á Á Á Á Á Á Á
CHART 1
30
40
50
60
70
80
-1
4
10
16
21
27
C
B
A
30
40
50
60
70
80
-1
4
10
16
21
27
Outdoor Air Not Suitable:
During the unoccupied time period dampers are closed.
During the occupied time period a cooling demand will open
dampers to minimum position and mechanical cooling
functions normally.
During the occupied time period dampers will open to DCV
MAX when IAQ reading is above setpoint (regardless of
thermostat demand or outdoor air suitability).
See table 16 for economizer operation with a standard two-
stage thermostat.
ris­
2
During the occupied period, dampers will open to DCV
MAX when IAQ reading is above setpoint (regardless of
thermostat demand or outdoor air suitability). DCV MAX will
NOT override damper fully open position. When an R1
mixed air sensor for modulating dampers is installed, DCV
MAX may override damper free cooling position when oc­
cupancy is high and outdoor air temperatures are low. If R1
senses discharge air temperature below 45_F (7_C),
dampers will move to minimum position until discharge air
temperature rises to 48_F (9_C).
TABLE 16
DAMPER POSITION
Á Á Á Á Á Á Á Á Á
OCCUPIED
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
CLOSED
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
MINIMUM
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
OPEN*
Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á
OPEN*
Á Á Á Á Á Á Á Á Á
Page 35
_F
90
100
_C
32
38
0
10
20
30
40
50
60
70
80
90
100
_F
90
100
_C
32
38
Outdoor Air Suitable:
Á Á Á Á Á Á Á Á Á Á Á
MECHANICAL COOLING
Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á Á
NO
Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á Á
NO
Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á Á
NO
Á Á Á Á Á Á Á Á Á Á Á
Á Á Á Á Á Á Á Á Á Á Á
STAGE 1
Á Á Á Á Á Á Á Á Á Á Á

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents