Lennox KGA Series Service Literature page 27

Units 7.5 to 12.5 ton, 26.3 to 42 kw
Table of Contents

Advertisement

TABLE 10
KGA150 NORMAL OPERATING PRESSURES
CIRCUIT 1
Outdoor
Dis­
Coil
Suction
charge
Entering
+10 psig
Air Temp
655 F
279
755 F
318
855 F
360
955 F
406
1055 F
456
1155 F
508
Charge Verification - Approach Method - AHRI Testing
1- Using the same thermometer, compare liquid tempera­
ture
(at condenser outlet)
ture.
Approach Temperature = Liquid temperature minus
ambient temperature.
2- Approach temperature should match values shown in
table 11. An approach temperature greater than
indicates an undercharge. An approach tempera­
ue
ture less than
this value
3- The approach method is not valid for grossly over­
charged or undercharged systems.
through 10
as a guide for typical operating pressures.
TABLE 11
APPROACH TEMPERATURE
Liquid Temp. Minus Ambient Temp.
Unit
1st Stage
092
9°F + 1 (5.0°C + 0.5)
102
7°F + 1 (3.9°C + 0.5)
120
8°F + 1 (4.4°C + 0.5)
150
6°F + 1 (3.3°C + 0.5)
V- SYSTEMS SERVICE CHECKS
A-Heating System Service Checks
All KGA units are ETL/CSA design certified without mod­
ification.
Before checking piping, check with gas company or au­
thorities having jurisdiction for local code requirements.
Refer to the KGA Installation instruction for more infor­
mation.
CIRCUIT 2
Dis­
Suction
charge
+5 psig
+10 psig
+5 psig
132
283
136
134
323
138
136
364
139
138
411
140
141
462
142
145
515
145
to outdoor ambient tempera­
indicates an overcharge.
Use tables
2nd Stage
8°F + 1 (4.4°C + 0.5)
6°F + 1 (3.3°C + 0.5)
6°F + 1 (3.3°C + 0.5)
6°F + 1 (3.3°C + 0.5)
REFER TO INSTALLATION INSTRUCTIONS
GROUND
JOINT UNION
MANUAL MAIN
SHUT-OFF VALVE
(REFER TO LOCAL CODES)
1-Gas Piping
Gas supply piping must not allow more than 0.5"W.C.
(124.3 Pa) drop in pressure between the gas meter and
the unit. Supply gas pipe must not be smaller than the unit
gas connection. Refer to installation instructions for de­
tails.
this val­
2-Testing Gas Piping
NOTE-In case emergency shutdown is required, turn off
the main manual shut‐off valve and disconnect the main
power to the unit. These controls should be properly la­
beled by the installer.
7
When pressure testing gas lines, the gas valve must be dis­
connected and isolated. Gas valves can be damaged if
subjected to more than 0.5 psig [14"W.C. (3481 Pa)]. See
figure 20.
When checking piping connection for gas leaks, use the
preferred means. Common kitchen detergents can
cause harmful corrosion on various metals used in gas
piping. The use of specialty Gas Leak Detector is strong­
ly recommended. It is available as part number
31B2001. See CORP 8411-L10, for further details.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.
3-Testing Gas Supply Pressure
When testing gas supply pressure, connect test gauge to the
inlet pressure tap located on unit gas valve GV1. Test sup­
ply gas pressure with unit firing at maximum rate (both
stages energized). Make sure the reading falls within the
range of the following values. Low pressure may result in
erratic operation or "underfire." High pressure can result in
permanent damage to the gas valve or "overfire." For nat­
ural gas units, operating pressure at the unit gas connec­
tion must be between 4.7"W.C. and 10.5"W.C. (1168 Pa
and 2610 Pa). For L.P. gas units, operating pressure at
the unit gas connection must be between 10.8"W.C. and
13.5"W.C. (2685.3 Pa and 3356.7 Pa).
Page 27
GAS PIPING COMPONENTS
CAP HERE TO
ISOLATE VALVE
WHEN PRESSURE
TESTING LINE
ROOF
MOUNTING
FRAME
DRIP LEG
GAS PIPING
SUPPORT
FIGURE 20
VALVE
UNIT

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents