S e r v i c e L i t e r a t u r e
The ZCC 7.5, 8.5, 10 and 12.5 ton (092, 102, 120, 150)
packaged electric units are available in standard cooling
efficiency.
All ZCC units are designed to accept any of several differ-
ent energy management thermostat control systems with
minimum field wiring. Factory or field provided control op-
tions connect to the unit with jack plugs. When "plugged
in" the controls become an integral part of the unit wiring.
Optional electric heat is field-installed. Electric heat op-
erates in single or multiple stages depending on the kW
input size. 7.5kW to 60kW heat sections are available for
ZCC units.
Information contained in this manual is intended for use
by qualified service technicians only. All specifications are
subject to change. Procedures outlined in this manual are
presented as a recommendation only and do not super-
sede or replace local or state codes.
If the unit must be lifted for service, rig unit by attaching
four cables to the holes located in the unit base rail (two
holes at each corner). Refer to the installation instructions
for the proper rigging technique.
WARNING
Improper
installation,
service or maintenance can cause property damage,
personal injury or loss of life. Installation and service
must be performed by a licensed professional HVAC
installer or equivalent service agency.
WARNING
To prevent serious injury or death:
1- Lock-out/tag-out before performing maintenance.
2- If system power is required (e.g., smoke detector
maintenance), disable power to blower, remove
fan belt where applicable, and ensure all
controllers and thermostats are set to the "OFF"
position before performing maintenance.
3- Always keep hands, hair, clothing, jewelry, tools,
etc., away from moving parts.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal
injury. Take care while handling this equipment and
wear gloves and protective clothing.
UNIT INFORMATION
UNIT INFORMATION
ZCC092 through 150
adjustment,
alteration,
100078
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect
switch(es). Unit may have multiple power
supplies.
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . Page 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Electrical Data /Electric Heat Data . . . . . . . . . . . . Page 10
Parts Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
I- Unit Components . . . . . . . . . . . . . . . . . . . . . . . Page 16
II- Placement and Installation . . . . . . . . . . . . . . . Page 27
III- Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 27
IV- Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28
V- System Service Checks . . . . . . . . . . . . . . . . . Page 33
VI- Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 33
VII- Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 34
VIII-Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . Page 41
Page 1
ZCC SERIES
7.5 to 12.5 ton
26.3 to 42 kW
WARNING

Table of Contents

Advertisement

Table of Contents
loading

Summary of Contents for Lennox ZCC Series

  • Page 1: Table Of Contents

    ZCC SERIES UNIT INFORMATION UNIT INFORMATION 7.5 to 12.5 ton 26.3 to 42 kW 100078 S e r v i c e L i t e r a t u r e ZCC092 through 150 The ZCC 7.5, 8.5, 10 and 12.5 ton (092, 102, 120, 150) packaged electric units are available in standard cooling efficiency.
  • Page 2: Options / Accessories

    OPT IONS / AC C ESSORIES Unit Model No Catalog Item Description Number 092 102 120 150 COOLING SYSTEM Condensate Drain Trap 22H54 Copper 76W27 Conventional Fin/Tube Condenser Coil Factory (Replaces Environ™ Coil System) (Required for Humiditrol Dehumidification option) ® Drain Pan Overflow Switch 74W42 Low Ambient Kits (0°F)
  • Page 3 OPT IONS / AC C ESSORIES Unit Model No Catalog Item Description Number 092 102 120 150 INDOOR AIR QUALITY Air Filters Healthy Climate High Efficiency Air Filters MERV 8 50W61 ® 20 x 25 x 2 (Order 4 per unit) 52W41 MERV 13 MERV 16...
  • Page 4 OPT IONS / AC C ESSORIES Unit Model No Catalog Item Description Number 092 102 120 150 ECONOMIZER Standard Economizer (Not for Title 24) Standard Economizer with Single Temperature Control 13U45 Downflow or Horizontal Applications - Includes Barometric Relief Dampers and Air Hoods Standard Economizer Controls (Not for Title 24) Single Enthalpy Control 21Z09...
  • Page 5: Specifications

    SP ECIFICATIO NS General Data Nominal Tonnage 7.5 Ton 8.5 Ton 10 Ton 12.5 Ton Model Number KCC092S4M KCC102S4M KCC120S4M KCC150S4M Efficiency Type Standard Standard Standard Standard Blower Type MSAV MSAV MSAV MSAV ® ® ® ® Multi-Stage Multi-Stage Multi-Stage Multi-Stage Air Volume Air Volume...
  • Page 6: Blower Data

    BLOWER DATA B ELT DR IVE - 7 .5 | 8 .5 TO N KCC092S4M AND KCC102S4M - BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 −...
  • Page 7 BLOWER D ATA B ELT DR IVE - 1 0 | 1 2 .5 TO N KCC120S4M AND KCC150S4M - BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 −...
  • Page 8 BLO WER DATA FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS Nominal Maximum Drive Kit Number RPM Range 590 - 890 800 - 1105 795 - 1195 3.45 730 - 970 3.45 940 - 1200 3.45 1015 - 1300 5.75 900 - 1135 5.75 1040 - 1315 5.75...
  • Page 9 BLO WER DATA CEILING DIFFUSERS AIR RESISTANCE - in. w.g. RTD11 Step-Down Diffuser FD11 Flush Air Volume 1 Side, 2 Ends All Ends & Sides Diffuser Unit Size 2 Ends Open Open Open 2400 0.21 0.18 0.15 0.14 2600 0.24 0.21 0.18 0.17...
  • Page 10: Electrical Data /Electric Heat Data

    ELECTRIC AL/ELECTRIC H EAT DATA 7 .5 TO N Model No. KCC092S4 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph Compressor 1 Rated Load Amps (Non-Inverter) Locked Rotor Amps Compressor 2 Rated Load Amps (Non-Inverter) Locked Rotor Amps 36.5...
  • Page 11 ELECTRIC AL/ELECTRIC H EAT DATA 8 .5 TO N Model No. KCC102S4 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph Compressor 1 Rated Load Amps (Non-Inverter) Locked Rotor Amps Compressor 2 Rated Load Amps 13.1 (Non-Inverter) Locked Rotor Amps...
  • Page 12 ELECTRIC AL/ELECTRIC H EAT DATA 1 0 TO N Model No. KCC120S4 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph Compressor 1 Rated Load Amps (Non-Inverter) Locked Rotor Amps Compressor 2 Rated Load Amps (Non-Inverter) Locked Rotor Amps 38.9...
  • Page 13 ELECTRIC AL/ELECTRIC H EAT DATA 1 2 .5 TO N Model No. KCC150S4 Voltage - 60Hz 208/230V - 3 Ph 460V - 3 Ph 575V - 3 Ph Compressor 1 Rated Load Amps 17.6 (Non-Inverter) Locked Rotor Amps 66.1 55.3 Compressor 2 Rated Load Amps 22.4...
  • Page 14 ELECTRIC H EAT CAPACITIES 7.5 kW 15 kW 22.5 kW 30 kW 45 kW 60 kW Volts Btuh No. of Btuh No. of Btuh No. of Btuh No. of Btuh No. of Btuh No. of Input Input Output Stages Input Output Stages Input...
  • Page 15: Parts Arrangement

    ZCC PARTS ARRANGEMENT 20 x 24 x 2” EVAPORATOR FILTERS COIL (BEHIND COIL) TERMINAL STRIP TB1 LOW VOLTAGE INVERTER TERMINAL STRIP BLOWER HOUSING CONDENSER FANS BLOWER MOTOR ELECTRIC HEAT (OPTIONAL) ELECTRIC HEAT CONDENSER CONTROLS COIL COMPRESSORS FIGURE 1 ZCC CONTROL BOX K1 K2 K264 TB13...
  • Page 16: I-Unit Components

    I-UNIT COMPONENTS 2-Terminal Strip TB1 All indoor thermostat connections will be to TB1 located in ELECTROSTATIC DISCHARGE (ESD) the control area. For thermostats without “occupied “ and Precautions and Procedures “unoccupied” modes, a factory installed jumper across ter- CAUTION minals R and OC should be in place. Electrostatic discharge can affect electronic 3-Condenser Fan Capacitors C1 &...
  • Page 17 ZCC PLUMBING AND COMPRESSOR CIRCUITS DETAIL INDOOR COIL STAGE 2 DRIERS OUTDOOR COIL STAGE 1 INDOOR COIL STAGE 1 STG1 STG2 OUTDOOR COIL STAGE 2 COMPRESSOR COMPRESSOR PRESSURE SWITCHES (120 only) (S16 120 only) FIGURE 4 Page 17...
  • Page 18 B-Cooling Components 2-High Pressure Switches S4 and S7 All units use independent cooling circuits consisting of The high pressure switch is an auto-reset SPST N.C. separate compressors, condenser coils and evaporator switch which opens on a pressure rise. S4 (first circuit) coils.
  • Page 19 OPERATION / ADJUSTMENT B-Blower Operation A-Three Scroll Compressor Voltage Phasing Initiate blower demand at thermostat according to instruc- tions provided with thermostat. Unit will cycle on thermo- Three phase scroll compressors must be phased sequen- stat demand. The following steps apply to applications tially to ensure correct compressor and rotation and op- using a typical electro-mechanical thermostat.
  • Page 20 D-Determining Unit CFM 6 - Units Equipped With An Inverter - Reconnect high pressure switches S4 and S7. NOTE - Units equipped a Variable Frequency Drive (VFD) TABLE 1 are designed to operate on balanced, three-phase power. Operating units on unbalanced three-phase power will re- MINIMUM AND MAXIMUM PULLEY ADJUSTMENT duce the reliability of all electrical components in the unit.
  • Page 21 3 - Measure belt deflection force. For a new 2 and 3hp PULLEY ALIGNMENT belt, the deflection force should be 5.0-7.0 lbs. (35- ALIGNED 48kPa). For a new 5hp belt, the deflection force should be 7-10lbs. (48-69kPa). A force below these values indicates an under- tensioned belt.
  • Page 22 D-Optional Electric Heat Components 3-High Temperature Limit S20, S157, S158, S15, S160 & S161 (Secondary) Table 3 shows electric heat fuse ratings. See Options/ Accessories section (see table of contents) for ZCC to Limits are SPST normally closed manual-reset thermostat EHA match-ups.
  • Page 23 Fuse F3, is housed in a fuse block which holds three fuses. Each fuse is connected in series with each leg of All ZCC series units with electric heat use an electric electric heat. Figure 11 and table 3 show the fuses used heat relay K9.
  • Page 24 SINGLE DISCONNECT INSTALLATIONS Note: J2 harness is provided in the EH kit. J2 is factory-installed in ZH units so J2 harness can be discarded in ZH installations. LOW VOLTAGE F4 FUSE HARNESS BLOCK SHORTER HARNESS TB13 PROVIDED IN THE SPPS KIT HORIZONTAL POWER ENTRY Note: TB2 line voltage terminals are on...
  • Page 25 ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT FIGURE 11 EHA 7.5, 15, 22.5, 30, 45, 60KW ELECTRIC HEAT SECTION PARTS ARRANGEMENT SECONDARY MENTS LIMIT S20 HE1 - HE6 SECONDARY SECONDARY LIMIT S20 LIMIT S20 ELECTRIC HEAT VESTIBULE SECONDARY LIMIT S20 SECONDARY LIMIT S20 SECONDARY LIMIT S20 ELECTRIC...
  • Page 26 TABLE 3 ZCC/ZHC ELECTRIC HEAT SECTION FUSE RATING FUSE (3 each) EHA QUANTITY VOLTAGES & SIZE F3 - 1 F3 - 2 F3 - 3 F3 - 4 208/230V 25 Amp 250V ----- ----- ----- 460V 15 Amp 600V ----- ----- ----- EHO075-7.5...
  • Page 27: Ii-Placement And Installation

    II-PLACEMENT AND INSTALLATION 4 - Each refrigerant circuit is separately charged with R-410A refrigerant. See unit rating plate for correct Make sure the unit is installed in accordance with the in- amount of charge. stallation instructions and all applicable codes. See acces- 5 - Refer to section IV CHARGING for proper method sories section for conditions requiring use of the optional to check refrigerant charge.
  • Page 28: Iv-Charging

    IV-CHARGING 3 - Measure the outdoor ambient temperature and the suction pressure. Refer to the appropriate WARNING circuit charging curve to determine a target liquid temperature. Refrigerant can be harmful if it is inhaled. Refrigerant Note - Pressures are listed for sea level applications. must be used and recovered responsibly.
  • Page 29 TABLE 4 ZG/ZC 092S Normal Operating Pressures - 581153-01 Outdoor Coil Entering Air Temperature 65 F 75 F 85 F 95 F 105 F 115 F Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc (psig) (psig) (psig) (psig) (psig)
  • Page 30 TABLE 5 ZG/ZC102S Normal Operating Pressures 581154-01 Outdoor Coil Entering Air Temperature 65 F 75 F 85 F 95 F 105 F 115 F Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc (psig) (psig) (psig) (psig) (psig) (psig) (psig)
  • Page 31 TABLE 6 ZG/ZC 120S Normal Operating Pressures - 581155-01 Outdoor Coil Entering Air Temperature 65 F 75 F 85 F 95 F 105 F 115 F Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc (psig) (psig) (psig) (psig) (psig)
  • Page 32 TABLE 7 ZG/ZC150S Normal Operating Pressures 581159-01 Outdoor Coil Entering Air Temperature 65 F 75 F 85 F 95 F 105 F 115 F Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc (psig) (psig) (psig) (psig) (psig) (psig) (psig)
  • Page 33: V- System Service Checks

    V- SYSTEMS SERVICE CHECKS NOTE-Filters must be U.L.C. certified or equivalent for use in Canada. A-Cooling System Service Checks BACK OF UNIT ZCC units are factory charged and require no further ad- justment; however, charge should be checked periodically LIFT UP AND PULL using the approach method.
  • Page 34: Vii-Accessories

    Clean the all-aluminum coil by spraying the coil steadily ASSEMBLED ROOF MOUNTING FRAME and uniformly from top to bottom. Do not exceed 900 psi or a 45 angle; nozzle must be at least 12 inches from the SUPPLY AIR RETURN AIR OPENING coil face.
  • Page 35 The mixed air temperature sensor (R1) measures the sup- TABLE 8 ply air sensible temperature. See figure 19. The outdoor Dampers will modulate to air sensible control is the default economizer control. An Sensors 55°F discharge air (RT6) outdoor air single sensible sensor, S175, is also provided. when: See table 8 for outdoor and return air (OA and RA) sensor OA temperature (S175)
  • Page 36 A6 Enthalpy Control LED’S TABLE 9 A steady green Free Cool LED indicates that outdoor air ENTHALPY CONTROL SETPOINTS is suitable for free cooling. When an optional IAQ sensor Control Setting Free Cooling Setpoint At 50% RH is installed, a steady green DCV LED indicates that the 73°...
  • Page 37 CHART 1 CALCULATE MINIMUM FRESH AIR PERCENTAGE MIXED AND RETURN AIR TEMPERATURE OUTDOOR AIR TEMPERATURE DCV Set and Max Settings Outdoor Air Not Suitable: Adjust settings when an optional IAQ sensor is installed. During the unoccupied time period dampers are closed. The DCV SET potentiometer is factory-set at approxi- During the occupied time period a cooling demand will mately 50% of the potentiometer range.
  • Page 38 TABLE 10 ECONOMIZER OPERATION-OUTDOOR AIR IS SUITABLE FOR FREE COOLING -- FREE COOL LED “ON” Damper Position Thermostat Demand Mechanical Cooling Unoccupied Occupied Closed Closed Closed Minimum Open* Open* Open* Open* Stage 1 * Dampers will open to maintain 55°F (13°C) supply air when an R1 mixed air sensor is installed. POWER EXHAUST FANS ECONOMIZER FIGURE 21...
  • Page 39 Standard Economizer Down Flow and Horizontal • Connect all female terminals to TB1 - Pink (24V) to R; Grey (GND) to ground; Yel (Cool 1) to Y1; and The standard economizer is used with ZC,ZG,ZH 092-150 Blue (Cool 2) to Y2. units in downflow air discharge applications.
  • Page 40 F-Power Exhaust Fan When the overflow switch closes, 24VAC power is inter- rupted and after a five second delay unit compressors are The power exhaust fan (PEF) requires an optional gravi- de-energized. Once the condensate level drops below the ty exhaust damper and economizer and is used in down- set level, the switch will open.
  • Page 41: Viii-Wiring Diagrams

    VIII-Wiring Diagrams and Sequence of Operation ZCC092/150 UNIT DIAGRAM Page 41...
  • Page 42 ZCC092/150 Sequence of Operation 2nd Stage Cooling (compressor B2 is energized) 5 - Second stage cooling demand 24VAC is routed Power: through TB1 and proves N.C. high pressure switch 1 - Line voltage from unit disconnect energizes S7. Compressor contactor K2 is energized. N.O. transformer T1.
  • Page 43 ELECTRONIC OR ELECTROMECHANICAL THERMOSTAT POWER: 1- Terminal strip TB1 energizes thermostat components with 24VAC. OPERATION: 2- TB1 receives data from the electronic thermostat A2 (Y1, Y2, Y3, W1, W2, G, OCP). The 24VAC signal from TB1 energizes the appropriate components for heat or cool demand. Page 43...
  • Page 44 ECONOMIZER STANDARD EFFICIENCY SEQUENCE OF OPERATION POWER: 1- Terminal strip TB1 energizes the economizer components with 24VAC. OPERATION: 2- Enthalpy sensor A7 and A62 (if differential enthalpy is used) communicates to the economizer control module A6 when to power the damper motor B7. 3- Economizer control module A6 supplies B7 with 0 - 10 VDC to control the positioning of economizer.
  • Page 45 ECONOMIZER HIGH PERFORMANCE / LOW LEAK SEQUENCE OF OPERATION POWER: Terminal strip TB1 energizes the economizer components with 24VAC. OPERATION: Enthalpy sensor A7 and A62 (if differential enthalpy is used) communicates to the economizer control module A6 when to power the damper motor B7.
  • Page 46 EHA-7.5, 15, 22.5, 30, 45 & 60kW Y VOLTAGE ZCC SERIES UNITS Page 46...
  • Page 47 EHA-7.5, 15, 22.5, 30, 45 & 60kW G, J VOLTAGE ZCC SERIES UNITS Page 47...
  • Page 48 Sequence of Operation - EHA 7.5, 15, 22.5, 30, 45, 60 kW - Y and G, J, M 4 - If S20 and S157 (S158 on Y-volt units) secondary NOTE: This sequence of operation is for all Electric Heat kW ratings Y through J voltages. Each step of operation electric heat limits remain closed, HE1 and HE2 is numbered and can be followed in sequence on the di- (HE3 and HE4 on Y-volt units) electric heat is...
  • Page 49 CB10-Circuit Breaker SPPS Terminal Block Low Voltage Control Harness Electric Heat Control Harness S48- Disconnect TB2- SPPS Terminal Block TB3- Electric Heat Terminal Block TB13- Unit Terminal Block SINGLE POWER SUPPLY WITH CB10/S48 MULTIPLE POWER SUPPLY WITH CB10/S48 Page 49...