Wiring Of The Electric Control Cabinet; Filed Wiring - Gree A Series Installation, Start-Up And Maintenance Manual

Inverter modular air-cooled chiller heat pump
Hide thumbs Also See for A Series:
Table of Contents

Advertisement

A Series Inverter Modular Air-cooled Chiller (Heat Pump)
LSQWRF65VM/
NaA-M
LSQWRF70VM/
NaA-M
Notes:
(1)The specifications of the breaker and power cable listed in the table above are
determined based on the maximum power (maximum amps) of the unit.
(2)The specifications of the power cable listed in the table above are applied to the
conduit-guarded multi-wire copper cable (like, JYV copper cable, consisting of PV
insulated wires and a PVC cable jacket) used at 45℃ and resistible to 90℃(GB/T
16895.15-2002). If the working condition changes, they should be modified according
to the related national standard.
(3)The specifications of the breaker listed in the table above are applied to the breaker
with the working temperature at 40℃. If the working condition changes, they should
be modified according to the related national standard.
7.3

Wiring of the Electric Control Cabinet

LSQWRF35VM/NaA-M,LSQWRF60VM/NaA-M, LSQWRF65VM/NaA-M,
LSQWRF70VM/NaA-M
7.4

Filed Wiring

Safety Codes
(1)All wiring shall comply with applicable codes and engineering requirements.
(2)All field wiring shall be performed by the qualified electrician.
(3)Never perform wiring before the power supply is cut off.
380V~415VAC 3Ph
50Hz
380V~415VAC 3Ph
50Hz
16
16
16
16
18
16
63
16
63