Electric Wiring - Gree Versati III GRS-CQ4.0PdG/NhH2-E Owner's Manual

Air-to-water heat pump
Table of Contents

Advertisement

Air-to-water Heat Pump All in One Versati
Silk Screen
W
Connector to the compressor phase-W
U
Connector to the compressor phase-U
V
Connector to the compressor phase-V
R-2
S-2
Connector to reactor (input)
T-2
R-1
S-1
Connector to reactor (input)
T-1
R
Connector to filter L1-F
S
Connector to filter L2-F
T
Connector to filter L3-F
COMM1
Reserved
COMM
Communication
CN1
Switch power input

18.2 Electric Wiring

18.2.1 Wiring principle
General principles
(1) Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of
regulations and engineering requirements.
(2) Only electricians holding qualification are allowed to perform wire connection on the site.
(3) Before connection work is started, the power supply must be shut off.
(4) Installer shall be responsible for any damage due to incorrect connection of the external circuit.
(5) Only copper wires are allowed to be used.
(6) Connection of power cable to the electric cabinet of the unit
(7) Power cables should be laid out through cabling trough, conduit tube or cable channel.
(8) Power cables to be connected into the electric cabinet must be protected with rubber or plastic to prevent
scratch by edge of metal plate.
(9) Power cables close to the electric cabinet of the unit must be fixed reliably to make the power terminal in
the cabinet free from an external force.
(10) Power cable must be grounded reliably.
Power cable specifications and Leakage switch types in the following list are recommended.
Model
GRS-CQ4.0Pd/NhH2-E(O)
GRS-CQ6.0Pd/NhH2-E(O)
GRS-CQ4.0PdG/NhH2-E(I)
GRS-CQ6.0PdG/NhH2-E(I)
GRS-CQ8.0Pd/NhH2-E(O)
GRS-CQ10Pd/NhH2-E(O)
GRS-CQ8.0PdG/NhH2-E(I)
GRS-CQ10PdG/NhH2-E(I)
Leakage
Power Supply
V,Ph,Hz
230VAC,1Ph,50Hz
230VAC,1Ph,50Hz
38
Specification
Minimum Sectional
Switch
Area of Earth Wire
(A)
(mm
16
1.5
16
1.5
20
6.0
20
6.0
25
4.0
25
4.0
40
6.0
40
6.0
SPLIT
TYPE
Minimum
Sectional
Area of Power
Supply Wire
2
2
)
(mm
)
1.5
1.5
6.0
6.0
4.0
4.0
6.0
6.0