General Specification - Honeywell Sensepoint XCD RFD Technical Handbook

Remote flammable detector
Hide thumbs Also See for Sensepoint XCD RFD:
Table of Contents

Advertisement

Sensepoint XCD RFD Technical Manual

14 General specification

Sensepoint XCD Transmitter
Use
Electrical
Construction
Material
Weight
Mounting
Cable Entries
Sensor Entry
Detectable Gases & Performance (See notes below)
Gas
Selectable Full
Scale Range
Sensepoint Standard Temperature Sensor
Flammable 1 to 8*
20 to 100%LEL
Sensepoint High Temperature Sensor
Flammable 1 to 8*
20%LEL
Flammable 1 to 8*
20 to 100%LEL
Plug-in Sensepoint XCD Catalytic Bead Sensors
Flammable 1 to 8* *
20 to 100%LEL
Plug-in Sensepoint XCD Infrared Sensors
Methane
20 to 100%LEL
Propane*
20 to 100%LEL
Carbon Dioxide*
2.00%Vol
*Contact Honeywell Analytics for availability
NOTES
Performance figures are taken at 20-25°C;
1. measured using a sample humidity of 50%RH, applicable between 10 and 90% of full scale,
2. measured using test units calibrated at 50% of full scale,
3. measured at 1000cc/min for Methane CAT, 500cc/min for Methane IR with calibration cup (S3KCAL).
Response time (T90) may increase when operating in lower or higher temperature conditions or when gas is introduced with the Weather Protection accessory (SPXCDWP) fitted. Methane IR
sensor is calibrated and linearised only for Methane. Should it be exposed to other HC then non linear response is expected. For linearised operation other than Methane contact HA for alternate
parts.
Methane IR is calibrated at the factory 50%LEL Methane (2.5%Vol). This calibration enables 100% functional test prior to dispatch. This calibration does not remove need for calibration & test as
part of commissioning at site. For gases other than Methane the unit has to be calibrated at site using target gas.Data represents typical values, and system conditioning may be required to achieve
stated result.
Contact HA for details.
* Extended operating temperature range of -40°C to +65°C (-40°F to +149°F) for all sensor except for IR, with an accuracy of +/- 30% of applied gas from -20°C to -40°C (-4°F to -40°F) and
+55°C to +65°C (+131°F to +149°F). Long term operation at this range may cause decline in sensor performance.
Contact Honeywell Analytics for any additional data or details.
Certification
China
Korea
European
International
North America
CE
Environmental
IP Rating
Operating Temperature
Operating Humidity
Operating Pressure
Storage Conditions
3-wire, 4-20mA, gas detector transmitter for use with remotely mounted flammable gas
detectors.
Input Voltage Range:
Max Power Consumption:
Current output
≥0.0<1.0 mA
4.0 mA to 20.0 mA
2.0 mA or 4.0 mA
22.0 mA
Terminals
Relays
Communication
Epoxy painted aluminium alloy or 316 Stainless Steel
Aluminium alloy: 1.7kg, 316 Stainless Steel: 3.7kg
Pole or wall mounting
2 x M20 (for ATEX/IECEx/AP Approval) , or 2 x 3/4"NPT (for cCSAus Approval)
M25 (for ATEX/IECEx/AP Approval) or 3/4"NPT (for cCSAus Approval)
Default
Steps
Selectable
Default
Range
Cal Gas
Range
Point
100%LEL
10%LEL
50%LEL
25 to 95% of
selected full
20%LEL
n/a
10%LEL
scale range
100%LEL
10%LEL
50%LEL
100%LEL
10%LEL
50%LEL
30 to 70% of
100%LEL
10%LEL
50%LEL
selected full
100%LEL
10%LEL
50%LEL
scale range
2.00%Vol.
n/a
1.00%Vol.
GB Ex d IIC T4 GB3836.1&2 -2000, PA, CCCF
KTL Ex d IIC T6 (-40ºC to +65ºC)
ATEX Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66
IEC Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66
cCSAus Class I, Division 1, Groups B, C & D/ Flammable Performance CSA C22.2 No.152 and ISA 60079-29-1(Only combustion gas detection portion of the instrument has been assessed)
EN50270:2015 EN6100-6-4:2007
IP66 in accordance with EN60529:1992, NEMA 4X (Tested by third party laboratory)
-40ºC to +65ºC/ -40ºF to +149ºF, (IR: -20ºC to +50ºC/ -4ºF to +122ºF)
Note: The detector display may become illegible at temperatures below -20°C, but the detector continues its gas monitoring
function. The display is not damaged and recovers when the temperature rises back above -20 °C.
Continuous 20-90%RH (non condensing), Intermittent 10-99%RH (non condensing)
90-110kPa
-25°C to +65°C (-13°F to +149°F)
12 to 32Vdc (24Vdc nominal)
Max 5 Watts. at 24Vdc (see section 2 regarding maximum in
rush current)
4-20mA (Source or Sink)
Fault (refer to table 5 section 12.3 for further details)
Normal gas measurement
Inhibit (during configuration/user settings)
Maximum over range
15 x screw terminals suitable for wire diameter 0.5mm
2
2.5mm
(20AWG to 13AWG).
3 x 5A@250VAC. Selectable normally open or normally closed
(switch) and energized/de-energized (programmable).
RS485, Modbus RTU
Response
Response
Accuracy
Cal
Time (T60)
Time (T90)
Secs
Secs
<25
<+/- 1.5%LEL -55°C / -67°F 80°C / 176°F
<25
<+/- 1.5%LEL -55°C / -67°F 150°C / 302°F 10%LEL▲
<10
<+/- 1.5%LEL -55°C / -67°F 150°C / 302°F 20%LEL▲
<6
<25
<+/- 1.5%LEL
<40
<+/- 1.5%LEL
<40
<+/- 1.5%LEL
<40
<+/-0.04%Vol.
49
SPXCDHMRFEN Issue 4_08-2016
2
Operating Temperature
Default Alarm Points
Min
Max
A1
20%LEL▲
40%LEL▲
15%LEL▲
40%LEL▲
-20°C / -4°F
55°C / 131°F
20%LEL▲
40%LEL▲
-20°C / -4°F
50°C / 122°F
20%LEL▲
40%LEL▲
-20°C / -4°F
50°C / 122°F
20%LEL▲
40%LEL▲
-20°C / -4°F
50°C / 122°F 0.40%V/V.▲ 0.80%V/V.▲
▲ - Rising Alarm ▼ - Falling Alarm